Danfoss VLT FC 102 Instruction Manual page 36

Hvac drive
Hide thumbs Also See for VLT FC 102:
Table of Contents

Advertisement

Application Set-up Examples
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
6
6
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
U - I
A53
Table 6.2 Analog Speed Reference (Current)
34
®
VLT
Parameters
Function
6-12 Terminal 53
4 mA*
Low Current
6-13 Terminal 53
20 mA*
High Current
6-14 Terminal 53
0 RPM
Low Ref./Feedb.
Value
6-15 Terminal 53
1500 RPM
High Ref./Feedb.
Value
+
* = Default Value
Notes/comments:
D IN 37 is an option.
-
4 - 20mA
HVAC Drive Instruction Manual
Setting
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
U - I
A53
Table 6.3 Speed Reference (using a Manual Potentiometer)
MG11AJ22 - Rev. 2013-09-13
Parameters
Function
Setting
6-10 Terminal 53
Low Voltage
0.07 V*
6-11 Terminal 53
10 V*
High Voltage
6-14 Terminal 53
0 RPM
Low Ref./Feedb.
Value
6-15 Terminal 53
1500 RPM
High Ref./Feedb.
Value
* = Default Value
≈ 5kΩ
Notes/comments:
D IN 37 is an option.