Danfoss VLT FC 102 Instruction Manual page 49

Hvac drive
Hide thumbs Also See for VLT FC 102:
Table of Contents

Advertisement

Diagnostics and Troubleshoo...
Troubleshooting
Check for a defective power card.
Check for a defective control card.
Check for a defective option card.
If a 24 V DC power supply is used, verify proper
supply power.
WARNING 47, 24 V supply low
The 24 V DC is measured on the control card. The external
24 V DC backup power supply may be overloaded;
otherwise, contact the Danfoss supplier.
WARNING 48, 1.8 V supply low
The 1.8 V DC supply used on the control card is outside of
allowable limits. The power supply is measured on the
control card. Check for a defective control card. If an option
card is present, check for an overvoltage condition.
WARNING 49, Speed limit
When the speed is not within the specified range in
4-11 Motor Speed Low Limit [RPM] and 4-13 Motor Speed High
Limit [RPM], the adjustable frequency drive shows a warning.
When the speed is below the specified limit in 1-86 Trip
Speed Low [RPM] (except when starting or stopping), the
adjustable frequency drive trips.
ALARM 50, AMA calibration failed
Contact your Danfoss supplier or Danfoss Service
Department.
ALARM 51, AMA check U
and I
nom
The settings for motor voltage, motor current and motor
power are wrong. Check the settings in parameters 1-20 to
1-25.
ALARM 52, AMA low I
nom
The motor current is too low. Check the settings.
ALARM 53, AMA motor too big
The motor is too big for the AMA to operate.
ALARM 54, AMA motor too small
The motor is too small for the AMA to operate.
ALARM 55, AMA parameter out of range
The parameter values of the motor are outside of the
acceptable range. AMA cannot run.
ALARM 56, AMA interrupted by user
The user has interrupted the AMA.
ALARM 57, AMA internal fault
Try to restart AMA again. Repeated restarts can overheat the
motor.
®
VLT
HVAC Drive Instruction Manual
nom
MG11AJ22 - Rev. 2013-09-13
ALARM 58, AMA Internal fault
Contact your Danfoss supplier.
WARNING 59, Current limit
The current is higher than the value in 4-18 Current Limit.
Ensure that Motor data in parameters 1-20 to 1-25 are set
correctly. Possibly increase the current limit. Be sure that the
system can operate safely at a higher limit.
WARNING 60, External interlock
A digital input signal is indicating a fault condition external
to the frequency converter. An external interlock has
commanded the frequency converter to trip. Clear the
external fault condition. To resume normal operation, apply
24 V DC to the terminal programmed for external interlock.
Reset the frequency converter.
WARNING 62, Output frequency at maximum limit
The output frequency has reached the value set in 4-19 Max
Output Frequency. Check the application to determine the
cause. Possibly increase the output frequency limit. Be sure
the system can operate safely at a higher output frequency.
The warning will clear when the output drops below the
maximum limit.
WARNING/ALARM 65, Control card over temperature
The cut-out temperature of the control card is 176 °F [80 °C].
Troubleshooting
Check that the ambient operating temperature is
within limits.
Check for clogged filters.
Check fan operation.
Check the control card.
WARNING 66, Heatsink temperature low
The frequency converter is too cold to operate. This warning
is based on the temperature sensor in the IGBT module.
Increase the ambient temperature of the unit. Also, a trickle
amount of current can be supplied to the frequency
converter whenever the motor is stopped by setting 2-00 DC
Hold/Preheat Current at 5% and 1-80 Function at Stop
ALARM 67, Option module configuration has changed
One or more options have either been added or removed
since the last power-down. Check that the configuration
change is intentional and reset the unit.
ALARM 68, Safe Stop activated
Safe stop has been activated. To resume normal operation,
apply 24 V DC to terminal 37, then send a reset signal (via
Bus, Digital I/O, or by pressing the reset key).
7
7
47

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents