Danfoss VLT FC 102 Instruction Manual page 69

Hvac drive
Hide thumbs Also See for VLT FC 102:
Table of Contents

Advertisement

Specifications
Relay outputs
Programmable relay outputs
Relay 01 Terminal number
Max. terminal load (AC-1)
1)
on 1-3 (NC), 1-2 (NO) (Resistive load)
Max. terminal load (AC-15)
1)
(Inductive load @ cosφ 0.4)
1)
Max. terminal load (DC-1)
on 1-2 (NO), 1-3 (NC) (Resistive load)
1)
Max. terminal load (DC-13)
(Inductive load)
Relay 02 (FC 302 only) Terminal number
1)
Max. terminal load (AC-1)
on 4-5 (NO) (Resistive load)
Max. terminal load (AC-15)
1)
on 4-5 (NO) (Inductive load @ cosφ 0.4)
Max. terminal load (DC-1)
1)
on 4-5 (NO) (Resistive load)
1)
Max. terminal load (DC-13)
on 4-5 (NO) (Inductive load)
1)
Max. terminal load (AC-1)
on 4-6 (NC) (Resistive load)
1)
Max. terminal load (AC-15)
on 4-6 (NC) (Inductive load @ cosφ 0.4)
1)
Max. terminal load (DC-1)
on 4-6 (NC) (Resistive load)
Max. terminal load (DC-13)
1)
on 4-6 (NC) (Inductive load)
Min. terminal load on 1-3 (NC), 1-2 (NO), 4-6 (NC), 4-5 (NO)
Environment according to EN 60664-1
1)
IEC 60947 part 4 and 5
The relay contacts are galvanically isolated from the rest of the circuit by reinforced isolation (PELV).
2)
Overvoltage Category II
3)
UL applications 300 V AC 2A
Control card, 10 V DC output
Terminal number
Output voltage
Max. load
The 10 V DC supply is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Control characteristics
Resolution of output frequency at 0–590 Hz
Repeat accuracy of Precise start/stop (terminals 18, 19)
System response time (terminals 18, 19, 27, 29, 32, 33)
Speed control range (open-loop)
Speed control range (closed-loop)
Speed accuracy (open-loop)
Speed accuracy (closed-loop), depending on resolution of feedback device
All control characteristics are based on a 4-pole asynchronous motor
®
VLT
HVAC Drive Instruction Manual
2)3)
Overvoltage cat. II
MG11AJ22 - Rev. 2013-09-13
1-3 (break), 1-2 (make)
240 V AC, 2 A
240 V AC, 0.2 A
60 V DC, 1 A
24 V DC, 0.1 A
4-6 (break), 4-5 (make)
400 V AC, 2 A
240 V AC, 0.2 A
80 V DC, 2 A
24 V DC, 0.1 A
240 V AC, 2 A
240 V AC, 0.2 A
50 V DC, 2 A
24 V DC, 0.1 A
24 V DC 10 mA, 24 V AC 20 mA
overvoltage category III/pollution degree 2
10.5 V ±0.5 V
1:100 of synchronous speed
1:1000 of synchronous speed
30–4000 rpm: error ±8 rpm
0–6000 rpm: error ±0.15 rpm
2
8
8
50
15 mA
± 0.003 Hz
≤± 0.1 ms
≤ 2 ms
67