Siemens ET 200S Manual page 544

Distributed i/o system
Hide thumbs Also See for ET 200S:
Table of Contents

Advertisement

Response Times
D.5
Response Times for Analog Input Modules
Conversion Time
The conversion time comprises the basic conversion time and the processing time
for the wire break monitoring diagnosis (see the technical specifications for the
2AI TC STANDARD in Section 12.15 and 2AI TC HIGH FEATURE, Section 12.16).
In integrative conversion processes, the integration time is included directly in the
conversion time.
Cycle Time
The analog/digital conversion and the transfer of the digitized measured values to
memory or to the backplane bus take place sequentially. In other words, the analog
input channels are converted one after the other. The cycle time, that is, the time
until an analog output value is converted again, is the sum of the conversion times
of all the activated analog output channels of the analog input modules. You should
deactivate unused analog input channels during parameter assignment in order to
reduce the cycle time. The conversion and integration time for a deactivated
channel is 0.
Figure D-5 provides you with an overview of what makes up the cycle time for an
n-channel analog input module.
Figure D-5
D.6
Response Times for Analog Output Modules
Conversion Time
The conversion time of the analog output channels comprises the time for the
transfer of the digitized output values from internal memory and the digital/analog
conversion.
D-6
Channel 0 conversion time
Channel 1 conversion time
Cycle Time of the Analog Input Module
Cycle Time
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07