Analog Electronic Modules
Measuring Ranges for Resistance-Type Sensors: 150W, 300W,
Table 12-31 SIMATIC S5 Format: Measuring Ranges 150Ω, 300Ω,
Measuring Range
150 W
300 W
> 176.37
> 352.73
176.37
352.73
150.07
300.14
150
300
0.07
0.14
0
0
Negative values
(not physically possible)
*
If the resistors are connected incorrectly
Measuring Ranges for Resistance-Type Sensors: 600W, 3000W,
Table 12-32 SIMATIC S5 Format: Measuring Ranges 600Ω, 3000Ω,
Measuring Range
600 W
3000W
> 705.47
> 3527.34
705.47
3527.34
600.29
3001.46
600
3000
0.29
1.46
0
0
Negative values
(not physically possible)
*
If the resistors are connected incorrectly
12-24
Units
(Deci-
(Deci-
12
11
10
9
8
mal)
2409
0
1
0
0 1 0 1 1 0 1 0 0 1 0 0 1 Overflow
2408
0
1
0
0 1 0 1 1 0 1 0 0 0 0 0 0 Overrange
2049
0
1
0
0 0 0 0 0 0 0 0 0 1 0 0 0
2048
0
1
0
0 0 0 0 0 0 0 0 0 0 0 0 0 Rated
1
0
0
0
0 0 0 0 0 0 0 0 0 1 0 0 0
0
0
0
0
0 0 0 0 0 0 0 0 0 0 0 0 0
–1
1
1
1
1 1 1 1 1 1 1 1 1 1 0 0 0 Under-
–360
1
1
1
1 0 1 0 0 1 1 0 0 0 0 0 0
–361
1
1
1
1 0 1 0 0 1 0 1 1 1 0 0 1 Underflow*
Units
(Deci-
(Deci-
12
11
10
9
8
mal)
2409
0
1
0
0 1 0 1 1 0 1 0 0 1 0 0 1 Overflow
2408
0
1
0
0 1 0 1 1 0 1 0 0 0 0 0 0 Overrange
2049
0
1
0
0 0 0 0 0 0 0 0 0 1 0 0 0
2048
0
1
0
0 0 0 0 0 0 0 0 0 0 0 0 0 Rated
1
0
0
0
0 0 0 0 0 0 0 0 0 1 0 0 0
0
0
0
0
0 0 0 0 0 0 0 0 0 0 0 0 0
–1
1
1
1
1 1 1 1 1 1 1 1 1 1 0 0 0 Under-
–360
1
1
1
1 0 1 0 0 1 1 0 0 0 0 0 0
–361
1
1
1
1 0 1 0 0 1 0 1 1 1 0 0 1 Underflow*
Data Word
7
6
5
4
3
2
1
0
X E O
Data Word
7
6
5
4
3
2
1
0
X E O
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
Range
range
range*
Range
range
range*