Requirements
S You must have set up an S7 station consisting of a power supply module and a
DP master (for example, CPU 315-2 DP). A CPU 315-2 DP was used as the
DP master in this example. However, any other DP master (IEC 61784-1:2002
Ed1 CP 3/1) could be used instead.
S STEP7 (as of V 5.0 with ServicePack 3) is fully installed on your programming
device (PG). You must be familiar with STEP7.
S The programming device must be connected to the DP master.
Installation
1. Mount the rail (35 mm x 7.5 mm or 15 mm) with a length of at least 210 mm on
a solid base.
2. Install the various modules on the rail beginning on the left (hook on, swing in,
move to the left). Adhere to the following sequence:
– IM151-1 STANDARD interface module
– TM-P15S23-A1 terminal module
– 4 x TM-E15S24-A1 terminal module
– TM-P15S23-A1 terminal module
– 4 x TM-E15S24-A1 terminal module
– Terminating module
3. Set the PROFIBUS address 3 on the IM 151-1 STANDARD interface module.
Figure 2-2
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
OFF
64
32
16
PROFIBUS address 3
Setting the PROFIBUS Address 3
Brief Instructions on Commissioning ET 200S
ON
8
4
2
1
2-3