General Technical Specifications
7.2
Electromagnetic Compatibility, Shipping and Storage
Conditions
Definition
Electromagnetic compatibility is the capability of an electrical device to function
satisfactorily in its electromagnetic environment without interfering with this
environment.
The ET 200S distributed I/O system also meets the requirements of the European
Union's EMC legislation. A requirement for this is that the ET 200S distributed I/O
system meets the specifications and directives concerning electrical installation.
Pulse-Shaped Interference
The following table shows the electromagnetic compatibility of the ET 200S
distributed I/O system when confronted with pulse-shaped interference.
Pulse-Shaped Interference
Electrostatic discharge
to IEC 61000-4-2
Burst pulses (rapid, transient interference)
to IEC 61000-4-4.
Surge to IEC 61000-4-5
Only with lightning conductors
(see the DP master manual and the SIMATIC NET PROFIBUS
Network Description)
S
Asymmetrical interconnection
S
Symmetrical interconnection
7-6
Tested with
Corresponds to
8 kV
3 (air discharge)
4 kV
2 (contact discharge)
2 kV (supply line)
2 kV (signal line)
2 kV (supply line)
2 kV (signal line/
data line)
1 kV (supply line)
1 kV (signal line/
data line)
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
Severity
3
3
3