Power Module Error Types
The diagnostic message is reported on channel 0 and applies to the whole module.
Table 6-12 Power Module Error Types
Power Modules Electronic
Modules
PM-E
PM-E
24–48 VDC/
24 VDC
120–230 VAC
–––
Digital Electronic Module Error Types
Table 6-13 Digital Electronic Module Error Types
Digital Electronic
Modules
2DI 24 VDC High Feature
4DI 24 VDC High Feature
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
Error Type
17
10001: Sensor or load
D
voltage missing
18
10010: Fuse defect
D
Error Type
1
00001: Short circuit
D
1
00001: Short circuit
D
(In connection with
IM151-1 BASIC /
IM151-1 STANDARD, as
of
6ES7 151-1AA02-0AB0,
IM151-1 FO
STANDARD, as of
6ES7 151-1AB01-0AB0)
or IM151-1 HIGH
FEATURE
26
11010: External fault
D
(In connection with
IM151-1 STANDARD, up
to
6ES7 151-1AA01-0AB0
or IM151-1 FO
STANDARD, up to
6ES7 151-1AB00-0AB0)
Commissioning and Diagnostics
Meaning
No supply voltage,
Correct the process
or inadequate
wiring. Check the
supply voltage.
supply voltage.
The fuse in the
Replace the fuse.
power module has
tripped.
Meaning
Short circuit of the
Correct the process
sensor supply. The
wiring (sensor
diagnostic
wiring).
message is issued
on channel 0 and
applies to the
whole module.
Short circuit of the
Correct the process
sensor supply. The
wiring (sensor
diagnostic
wiring).
message is issued
on channel 0 and
applies to the
whole module.
What to Do
What to Do
6-41