Siemens ET 200S Manual page 43

Distributed i/o system
Hide thumbs Also See for ET 200S:
Table of Contents

Advertisement

Configuration
1. Start SIMATIC Manager, and create a new project with a DP master (CPU315-2
DP, for example). Create OB1 and OB82 for the project.
2. Create the PROFIBUS subnet.
3. Connect the PROFIBUS subnet with the DP master in HW Config.
4. Take the ET 200S from the hardware catalog and put it on the PROFIBUS.
5. Set the PROFIBUS address 3 for the ET 200S.
6. Drag the various ET 200S modules from the hardware catalog to the
configuration table.
7. Mark the electronic modules in the configuration table, and click the "Pack
addresses" button.
Table 2-1
Configuration Table in HW Config
Module/DP
Identifier
1
6ES7 138-4CA00-0AA0 PM-E 24 VDC
2
6ES7 131-4BB00-0AB0 2DI 24 VDC
3
6ES7 131-4BB00-0AB0 2DI 24 VDC
4
6ES7 131-4BB00-0AB0 2DI 24 VDC
5
6ES7 131-4BB00-0AB0 2DI 24 VDC
6
6ES7 138-4CA00-0AA0 PM-E 24 VDC
7
6ES7 132-4BB00-0AB0 2DO 24 VDC
8
6ES7 132-4BB00-0AB0 2DO 24 VDC
9
6ES7 132-4BB00-0AB0 2DO 24 VDC
10
6ES7 132-4BB00-0AB0 2DO 24 VDC
8. Set the following parameters:
– In the DP Slave Properties dialog box for ET 200S:
Startup when expected <> actual configuration: Enable
Replace modules during operation: Enable
– In the DP Slave Properties dialog box for the PM-E 24 VDC, Module/DP
ID 1 (in the configuration table)
Diagnostics: No load voltage
– In the Slave DP Properties dialog box for 2 DO 24 VDC, Module/DP ID 7 (in
the configuration table)
Diagnostics: Wire break O0
9. Save the configuration.
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
Order Number
Brief Instructions on Commissioning ET 200S
I
O
Address
Address
0
0
Comment
Power module
Bits 0.0 and 0.1
Bits 0.2 and 0.3
Bits 0.4 and 0.5
Bits 0.6 and 0.7
Power module
Bits 0.0 and 0.1
Bits 0.2 and 0.3
Bits 0.4 and 0.5
Bits 0.6 and 0.7
2-5