Analog Electronic Modules
Conversion time (per
channel)
Settling time
S
For resistive load
S
For capacitive load
S
For inductive load
Suppression of Interference, Limits of Error
Crosstalk between the
outputs
Operational limit (in the
entire temperature range,
with reference to the output
range)
Basic error limit (operational
limit at 25 _C with reference
to output range)
Temperature error (with
reference to the output
range)
Linearity error (with
reference to the output
range)
Repeatability
(in steady state at 25 _C
with reference to output
range)
Output ripple (with
reference to output range,
bandwidth 0 to 50 kHz)
12-138
Max. 1.0 ms
Output range (rated value)
0.25 ms
Load impedance (in the
rated range of the output)
1.0 ms
S
0.5 ms
Current output
> 60 dB
S
"0.05%
Destruction limit against
voltages/currents applied
from outside
S
"0.01%
S
"0.001%/K
Connection of actuators
Connection of actuators
"0.02%
S
"0.01%
"0.02%
Data for Selecting an Actuator
"20 mA
4 to 20 mA
Max. 500 W
For current outputs
For inductive load
1 mH
No-load voltage
18 V
Voltage at the outputs to
Max. 15 V
M
continuous; 75 V for
ANA
max. 1 s (pulse duty
factor 1:20)
Current
Max. DC 50 mA
Current output
Two-conductor
Possible
connection
Distributed I/O System ET 200S