Siemens ET 200S Manual page 500

Distributed i/o system
Hide thumbs Also See for ET 200S:
Table of Contents

Advertisement

4 IQ-SENSE
Diffuse sensor
Diffuse Sensor
Transmitter
Receiver
Transmitter
Receiver
Figure 13-2
Reflex sensor
Reflex Sensor
Transmitter
Receiver
Transmitter
Receiver
Figure 13-3
13.1.4
Switching Hysteresis Parameter
Features
Faults with the diffuse sensor or in the production process can result in signal
wobbles. The measured value then changes the switching threshold by 100 %
(object detected – object not detected). You can prevent this switching threshold
wobble using the switching hysteresis parameter. This will ensure a stable output
signal on the sensor.
You can parameterize 5%/10%/20%/50% for switching hysteresis.
13-6
Object
Ä Ä Ä
Ä Ä Ä
Ä Ä Ä
Diffuse Sensor
Object
Ä Ä Ä
Ä Ä Ä
Ä Ä Ä
Reflex Sensor
Circuit state 0: No object detected. In other
words, the object is not in the path of the
beams. The receiver cannot see any light.
Circuit state 1: Object detected. In other
words, the object is in the path of the be-
ams. The receiver sees some light.
Circuit state 0: No object detected. In other
words, the object is not in the path of the
beams. The receiver sees some light.
Circuit state 1: Object detected. In other
words, the object is in the path of the be-
ams. The receiver cannot see any light.
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07

Advertisement

Table of Contents
loading

This manual is also suitable for:

6es7 151-1aa00-8xa0