Measuring Range for Thermocouple Type N
Table 12-20 SIMATIC S7 Format: Measuring Range Type N in °C and °F
Units
Type N
in 5C
Dec.
Hex.
> 1550.0
32767
7FFF
1550.0
15500
3C8C
:
:
:
1300.1
13001
32C9
1300.0
13000
32C8
:
:
:
–270.0
–2700
F574
< –270.0
–32768
8000
Measuring Range for Thermocouple Types R, S
Table 12-21 SIMATIC S7 Format: Measuring Range Type R, S in °C and °F
Units
Types R, S
Types R, S
in 5C
Dec.
Hex.
> 2019.0
32767
7FFF
2019.0
20190
4EDE
:
:
:
1769.1
17691
451B
1769.0
17690
451A
:
:
:
–50.0
–500
FE0C
–50.1
–510
FE0B
:
:
:
–170.0
–1700
F95C
< –170.0
–32768
8000
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
Units
Type N
in 5F
Dec.
> 2822.0
32767
H
2822.0
28220
H
:
:
2372.1
23721
H
2372.0
23720
H
:
:
–454.0
–4540
H
–32768
8000
H
H
Units
Types R,
Types R,
S
Dec.
in 5F
> 3276.6
32767
H
3276.6
32766
H
:
:
3216.3
32163
H
3216.2
32162
H
:
:
–58.0
–580
H
–58.1
–581
H
:
:
–274.0
–2740
H
< –274.0
–32768
H
Analog Electronic Modules
Hex.
7FFF
Overflow
H
6E3C
H
:
Overrange
5CA9
H
5CA8
H
:
Rated range
EE44
H
<EE44
Underflow
H
Hex.
7FFF
Overflow
H
7FFE
H
:
Overrange
7DA3
H
7DA2
H
:
Rated range
FDBC
H
FDBB
H
:
Underrange
F54C
H
8000
Underflow
H
Range
Range
12-17