Connecting Inputs; Connecting The Inputs On The Dmi - Eaton NZM2 Manual

Circuit-breaker communication system
Hide thumbs Also See for NZM2:
Table of Contents

Advertisement

DMI
22
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Connecting inputs

The inputs of the DMI are switched electronically and are
isolated from each other and from other electronic circuitry
by means of optocouplers.
+ 24 V
0 V
F1
+24 V 0 V 0 V I0+ I0-
Figure 4: Connecting the inputs on the DMI
Connect the input terminals (I0+/I0– to I5+/I5–) to auxiliary
contacts or other relevant contacts from the vicinity of the
circuit-breaker.
Two-wire proximity switches cant be used due to their high
residual current.
The inputs are polarised, i.e. on I0+ the pole must be
connected to the positive potential, and I0– must be
connected with the corresponding reference point.
h
Polarity reversal will not damage the DMI, but will prevent
the relevant switching states from being indicated and
evaluated.
The current and voltage ranges for the digital inputs are
stated in a section "Digital inputs (24 V DC)", Page 71.
11/04 MN01219002Z-EN
24 V
...
I5+ I5-

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nzm3Nzm4

Table of Contents