Eaton NZM2 Manual page 104

Circuit-breaker communication system
Hide thumbs Also See for NZM2:
Table of Contents

Advertisement

11/04 MN01219002Z-EN
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
h
The delta mode, motor "ON", motor anticlockwise, motor
clockwise, motor state and star mode data content are
compiled from the control signals of the DMI outputs to
which the contactor relays for motor control are connected
(a section "Motor starter", Page 44). They therefore
only conditionally reflect the state of the motor control.
Format of the data outputs
Writing of the data outputs is implemented directly via the
DPV0 write commands or via the output bytes of the DP
master defined by the PROFIBUS-DP configuration. Note the
documentation of the master device for this purpose. Three
octets are written as data outputs and contain the following
control information:
Table 13: Address assignment of the module 3 data outputs
Data position
Octet 1
Bit 0 and Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Octet 2
Bit 0 to Bit 4
Bit 5
Bit 6 and Bit 7
Octet 3
Bit 0
Bit 1
Bit 2 to Bit 7
PROFIBUS-DPV0 functions
Designation
Operation circuit-breaker
Not used
Output 0
Output 1
Output 2
Output 3
Output 4
Not used
Output 5
Not used
Motor "ON" or motor anticlockwise
rotation
Motor clockwise rotation
Not used
99