Eaton NZM2 Manual page 116

Circuit-breaker communication system
Hide thumbs Also See for NZM2:
Table of Contents

Advertisement

11/04 MN01219002Z-EN
Designation
Overflow of additional
diagnosis information
Parameterization fault
Parameterization query
Parameterized motor-
starter function changed
or deactivated
Remote operator not
parameterized in DMI
Slave deactivated
Slot number
Static diagnosis
Station not existent
Station not ready
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Meaning
The additional diagnosis data
(status) is larger than the memory
reserved for it in the DP master
The DP master has sent an invalid
parameterization telegram to the
NZM-XDMI-DPV1
The NZM-XDMI-DPV1 waits for the
parameterization telegram of the DP
master
A motor starter function which has
already been parameterized in the
DMI is changed or deactivated
The remote operator in the DMI is
not parameterized, the switch state
of the circuit-breaker can not be
controlled via the PROFIBUS
The DP master has removed the
NZM-XDMI-DPV1 from its cyclic
process routine (deactivated)
Contains the slot number from which
the additional diagnosis information
(status) originates:
hexadecimal 00
The communication between the
NZM-XDMI-DPV1 and DMI is
interrupted
A station does not answer at the
station address used
The NZM-XDMI-DPV1 is not yet
ready for communication
(initialization phase)
PROFIBUS-DPV0 functions
Clarification/Hint
Check the configuration of the
DP master
Check the configuration of the
DP master
Temporary state
Parameterize the remote
operator in the DMI
Intended user action
Check the connection between
the DMI and NZM-XDMI-DPV1
Inspect the configuration of the
DP master and the address
setting on the DMI
Temporary state
111