Circuit-breaker communication system
Hide thumbs Also See for NZM2:
Table of Contents

Advertisement

11/04 MN01219002Z-EN
Designation
Motor clockwise
Motor anticlockwise
Not used
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Meaning
00
Switch off motor
01
Switch on motor for
anticlockwise rotation
10
Switch on motor for
clockwise rotation
11
Not permissible
No information for
evaluation
Module 4 conform to PROFIBUS circuit-breaker
profile 2 and motor starter
When this module is selected, the following additional
information can be read out from the circuit-breaker and the
DMI in addition to the information of module 2:
• Motor switched on/off,
• Motor rotation left/right,
• Motor star connection,
• Motor delta connection.
Furthermore, the following functions can be controlled in
addition to the functions of module 2:
• Switch motor on/off,
• Switch motor rotation to anticlockwise/clockwise.
The information read out are data inputs of the DP master,
the controllable functions are picked up in the DP master as
data outputs.
h
This information and these functions are only available if
a motor starter function has been parameterized in the
DMI.
PROFIBUS-DPV0 functions
Precondition
Outputs 0 and 1 have been
parameterized for "reversing
starter" or the outputs 0, 1, 2 and
3 have been parameterized for
"star-delta-reversing starter"
101