11/04 MN01219002Z-EN
Error message
Invalid parameter
(Code B8
hexadecimal)
Invalid range
(Code B7
hexadecimal)
Invalid slot
(Code B2
hexadecimal)
Resource
unavailable
(Code C3
hexadecimal)
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Meaning
The data length used with the
Read service is smaller than
the data length of the accessed
object
The parameters used with
connection set-up of the
class 2 DPV1 master do not
correspond with those of the
NZM-XDMI-DPV1
You have selected an
inconsistent parameterization
for the motor starter or remote
operator function when
writing the "DMI output
assignment " object
An invalid value has been used
for the data content with a
Write service
The slot defined in the Read or
Write service is invalid for the
NZM-XDMI-DPV1
The accessed object can
currently not be contacted as
either communication
between NZM-XDMI-DPV1
and DMI or between the DMI
and circuit-breaker has
malfunctioned
You have selected a record
number when reading the
"Circuit-breaker diagnostics
record" for which there is
currently no entry
PROFIBUS-DPV1 functions
Clarification/Hint
Use the data length defined in the object
description
The Features Supported parameter must be
set to "1" and the Ident Number profile to
"0" on the class 2 DPV1 master with
connection set-up.
Please note the object description
Please observe the value range of the data
content as described in the object
description
Use the slot defined in the object
description
Check the connection between the devices
Select a lower record number