Circuit-breaker communication system
Hide thumbs Also See for NZM2:
Table of Contents

Advertisement

NZM-XDMI-DPV1
(PROFIBUS-DPV1 Interface for
DMI)
146
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Note
Trip of the circuit-breaker by this command can only be
achieved when current is flowing.
Addressing and length of the object
Please use the following information for addressing of the
object:
• API is equal to 0 (only required for class 2 DPV1 master),
• Slot number is equal to 0,
• The index is equal to 16.
The length of the data to be written is 1 Octet. Please ensure
that you do not enter other lengths when calling the Write
service as otherwise you will receive a fault indication.
Variable definitions (example) for the object
According to IEC 61131-3, you define the following variable
(data module):
Name
LS_DMI_command
Format and meaning of the object data content
The following table displays the address location and the
meaning of the data content of the object. Furthermore, it
provides an example of how the data content can be
accessed by the application with the aid of the example
variable.