NZM-XDMI-DPV1
(PROFIBUS-DPV1 Interface for
DMI)
130
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
h
After a circuit-breaker trip, the trip conditions are retained
until they are acknowledged with the aid at the "circuit-
breaker/DMI command" .
Addressing and length of the object
Please use the following information for addressing of the
object:
• API is equal to 0 (only required for class 2 DPV1 master),
• Slot number is equal to 0,
• The index is equal to 11.
The length of the data to be read is 7 Octets. Please ensure
that you do not enter smaller lengths when calling the Read
service as otherwise you will receive a fault indication.
Variable definitions (example) for the object
According to IEC 61131-3, you define the following variable
(data module):
Name
LS_Status
Format and meaning of the object data content
The following table displays the address location and the
meaning of the data content of the object. Furthermore, it
provides an example of how the data content can be
accessed by the application with the aid of the example
variable.
11/04 MN01219002Z-EN
Data type
ARRAY [1..56] OF BOOL or
ARRAY [1..7] OF BYTE