PATRZ KARTA - NZM3-XR220-250DC
Napęd zdalny, 220-250VDC, do rozmiaru 3
Typ
Catalog No.
Abbildung ähnlich
Program dostaw
Asortyment
Akcesoria
Nominalna częstotliwość robocza
Norma/Dopuszczenie
Wielkość gabarytowa
Opis
Closing delay
Break time
Napięcie sterownicze pomiaru
28.02.2018
NZM3-XR220-250DC
259860
ms
ms
U
V
s
Eaton 259860 ED2018 V41.0 PL
Akcesoria
Napęd zdalny ze zdolnością synchronizacji.
DC
UL/CSA, IEC
NZM3
For remote switching of circuit-breakers and switch-disconnectors.
ON and OFF switching and resetting by means of two-wire or three-wire control.
Local switching by hand possible.
Lockable in the 0 position of the remote operator with up to 3 padlocks (hasp
thickness: 4 – 8 mm)
Can be synchronized
Please note during engineering:
Three-wire control
Terminal 70/71:
NZM-XR: Contact loading
according to technical data
NZM2-XRD: Full current flows
through the contact during make
and break!
RMQ series contact elements
can be used for the NZM2(3.4)-
XR(D)...remote operators.
Two-wire control
Terminal 75:
NZM-XR: Operational readiness
signal when cover closed and not
locked.
NZM2-XRD: Operational readiness
signal when sliding switch set to
Auto.
Sliding switch with three positions:
Manual/Auto/Locked for reliable
differentiation of connected
positions.
AC-15: 400 V; 2 A
DC-13: 220 V; 0.2 A
Three-wire control with automatic reset to the 0 position after the
switch has tripped
Switching cycle:
NZM2-XR
NZM3-XR
NZM4-XR
The time interval between OFF and ON is 3 seconds. On commands
received during the time interval are ignored within the first 3 seconds
after switch off.
Parallel remote operator connection
80
1000
220 - 250 V DC
1 / 3