28
Device Description
3.6
Technical Data
3.6.1
Housing
Table 12: Technical Data Housing
Dimensions (W x H x L)
Weight
Operating temperature
Storage temperature
Type of mounting
Degree of protection
Wire connection
Cross section
Stripped length
3.6.2
Supply
Table 13: Technical Data Supply
Operating voltage
Nominal voltage, operation with mains
power
Nominal voltage, operation using
battery
Bias current
(with +24 VDC power supply, without
external protective circuit)
Current for transmission
(with +24 VDC power supply)
3.6.3
GSM Antenna Connection
Table 14: Technical Data GSM Antenna Connection
Connection
Cable length (max.)
Bandwidth
Gain
Impedance
Input power
VSWR (max.)
VSWR (recommended)
WAGO-TO-PASS® 761
761-112 Telecontrol Module Compact, Web
109 mm x 105 mm x 78 mm
Approx. 412 g
-20 °C ... +70 °C
-40 °C ... +85 °C
DIN 35 rail
IP 20
Terminal strips (WAGO 250 Series)
with push-wire connection
0,5 mm² ... 1,0 mm²
AWG 22 ... AWG 14 „sol"
9 mm ... 10 mm
+10 V ... +30 VDC
+24 VDC
+12 VDC
approx. 20 mA
< 500 mA
SMA socket
30 m
70 MHz in GSM (850 MHz)
80 MHz in EGSM (900 MHz)
170 MHz in DCS (1800 MHz)
140 MHz in PCS (1900 MHz)
< 3 dBi
50 Ohm
> 2 W (peak power)
<= 10:1
<= 2:1
Manual
Version 2.0.0