Figure 149. Oil injection solenoid valve
Table 75. Oil charge per compressor
Compressor
CSHN374
CSHN176 thru 315 and VZH170
Table 76. Torque requirements for rotolock fittings
CSHN* and VZH170
N N o o t t e e : : Always replace gasket when reassembling oil
equalizer lines.
VFD Programming Parameters (Supply/
Return/Exhaust Inverters)
W W A A R R N N I I N N G G
H H a a z z a a r r d d o o u u s s V V o o l l t t a a g g e e w w / / C C a a p p a a c c i i t t o o r r s s ! !
F F a a i i l l u u r r e e t t o o d d i i s s c c o o n n n n e e c c t t p p o o w w e e r r a a n n d d d d i i s s c c h h a a r r g g e e
c c a a p p a a c c i i t t o o r r s s b b e e f f o o r r e e s s e e r r v v i i c c i i n n g g c c o o u u l l d d r r e e s s u u l l t t i i n n d d e e a a t t h h o o r r
s s e e r r i i o o u u s s i i n n j j u u r r y y . .
D D i i s s c c o o n n n n e e c c t t a a l l l l e e l l e e c c t t r r i i c c p p o o w w e e r r , , i i n n c c l l u u d d i i n n g g r r e e m m o o t t e e
d d i i s s c c o o n n n n e e c c t t s s a a n n d d d d i i s s c c h h a a r r g g e e a a l l l l m m o o t t o o r r s s t t a a r r t t / / r r u u n n
c c a a p p a a c c i i t t o o r r s s b b e e f f o o r r e e s s e e r r v v i i c c i i n n g g . . F F o o l l l l o o w w p p r r o o p p e e r r
l l o o c c k k o o u u t t / / t t a a g g o o u u t t p p r r o o c c e e d d u u r r e e s s t t o o e e n n s s u u r r e e t t h h e e p p o o w w e e r r
c c a a n n n n o o t t b b e e i i n n a a d d v v e e r r t t e e n n t t l l y y e e n n e e r r g g i i z z e e d d . . F F o o r r v v a a r r i i a a b b l l e e
f f r r e e q q u u e e n n c c y y d d r r i i v v e e s s o o r r o o t t h h e e r r e e n n e e r r g g y y s s t t o o r r i i n n g g
c c o o m m p p o o n n e e n n t t s s p p r r o o v v i i d d e e d d b b y y T T r r a a n n e e o o r r o o t t h h e e r r s s , , r r e e f f e e r r t t o o
t t h h e e a a p p p p r r o o p p r r i i a a t t e e m m a a n n u u f f a a c c t t u u r r e e r r ' ' s s l l i i t t e e r r a a t t u u r r e e f f o o r r
a a l l l l o o w w a a b b l l e e w w a a i i t t i i n n g g p p e e r r i i o o d d s s f f o o r r d d i i s s c c h h a a r r g g e e o o f f
c c a a p p a a c c i i t t o o r r s s . . V V e e r r i i f f y y w w i i t t h h a a C C A A T T I I I I I I o o r r I I V V v v o o l l t t m m e e t t e e r r
r r a a t t e e d d p p e e r r N N F F P P A A 7 7 0 0 E E t t h h a a t t a a l l l l c c a a p p a a c c i i t t o o r r s s h h a a v v e e
d d i i s s c c h h a a r r g g e e d d . .
F F o o r r a a d d d d i i t t i i o o n n a a l l i i n n f f o o r r m m a a t t i i o o n n r r e e g g a a r r d d i i n n g g t t h h e e s s a a f f e e
d d i i s s c c h h a a r r g g e e o o f f c c a a p p a a c c i i t t o o r r s s , , s s e e e e P P R R O O D D - - S S V V B B 0 0 6 6 * * - - E E N N . .
Units shipped with an optional variable frequency drive
(VFD) are preset and run tested at the factory. If a
problem with a VFD occurs, ensure that the
RT-SVX24Q-EN
Pints
15.2
14.2
100 +/- 10 ft-lbs
S S e e r r v v i i c c e e a a n n d d M M a a i i n n t t e e n n a a n n c c e e
programmed parameters listed in
been set before replacing the drive.
V V e e r r i i f f y y P P a a r r a a m m e e t t e e r r s s
Verify parameter 1-23 is set to 60 Hz.
1. To check parameter 1-23 press the Main Menu
button twice (if TR150 drive) (press the Back button
if the main menu does not display)
2. Scroll down to Load & Motor, press OK
3. Select 1-2, press OK
4. Press down until parameter 1-23 is displayed.
Parameter 1-23 can then be modified by pressing
OK and pressing the Up and Down buttons.
5. When the desired selection has been made, press
OK .
Should replacing the VFD become necessary, the
replacement is not configured with all of Trane's
operating parameters. The VFD must be programmed
before attempting to operate the unit.
To verify and/or program a VFD, use the following
steps:
1. At the unit, turn the 115 volt control circuit switch to
the Off position.
2. Turn the 24 volt control circuit switch to the Off
position.
W W A A R R N N I I N N G G
H H a a z z a a r r d d o o u u s s V V o o l l t t a a g g e e w w / / C C a a p p a a c c i i t t o o r r s s ! !
F F a a i i l l u u r r e e t t o o d d i i s s c c o o n n n n e e c c t t p p o o w w e e r r a a n n d d d d i i s s c c h h a a r r g g e e
c c a a p p a a c c i i t t o o r r s s b b e e f f o o r r e e s s e e r r v v i i c c i i n n g g c c o o u u l l d d r r e e s s u u l l t t i i n n d d e e a a t t h h o o r r
s s e e r r i i o o u u s s i i n n j j u u r r y y . .
D D i i s s c c o o n n n n e e c c t t a a l l l l e e l l e e c c t t r r i i c c p p o o w w e e r r , , i i n n c c l l u u d d i i n n g g r r e e m m o o t t e e
d d i i s s c c o o n n n n e e c c t t s s a a n n d d d d i i s s c c h h a a r r g g e e a a l l l l m m o o t t o o r r s s t t a a r r t t / / r r u u n n
c c a a p p a a c c i i t t o o r r s s b b e e f f o o r r e e s s e e r r v v i i c c i i n n g g . . F F o o l l l l o o w w p p r r o o p p e e r r
l l o o c c k k o o u u t t / / t t a a g g o o u u t t p p r r o o c c e e d d u u r r e e s s t t o o e e n n s s u u r r e e t t h h e e p p o o w w e e r r
c c a a n n n n o o t t b b e e i i n n a a d d v v e e r r t t e e n n t t l l y y e e n n e e r r g g i i z z e e d d . . F F o o r r v v a a r r i i a a b b l l e e
f f r r e e q q u u e e n n c c y y d d r r i i v v e e s s o o r r o o t t h h e e r r e e n n e e r r g g y y s s t t o o r r i i n n g g
c c o o m m p p o o n n e e n n t t s s p p r r o o v v i i d d e e d d b b y y T T r r a a n n e e o o r r o o t t h h e e r r s s , , r r e e f f e e r r t t o o
t t h h e e a a p p p p r r o o p p r r i i a a t t e e m m a a n n u u f f a a c c t t u u r r e e r r ' ' s s l l i i t t e e r r a a t t u u r r e e f f o o r r
a a l l l l o o w w a a b b l l e e w w a a i i t t i i n n g g p p e e r r i i o o d d s s f f o o r r d d i i s s c c h h a a r r g g e e o o f f
c c a a p p a a c c i i t t o o r r s s . . V V e e r r i i f f y y w w i i t t h h a a C C A A T T I I I I I I o o r r I I V V v v o o l l t t m m e e t t e e r r
r r a a t t e e d d p p e e r r N N F F P P A A 7 7 0 0 E E t t h h a a t t a a l l l l c c a a p p a a c c i i t t o o r r s s h h a a v v e e
d d i i s s c c h h a a r r g g e e d d . .
F F o o r r a a d d d d i i t t i i o o n n a a l l i i n n f f o o r r m m a a t t i i o o n n r r e e g g a a r r d d i i n n g g t t h h e e s s a a f f e e
d d i i s s c c h h a a r r g g e e o o f f c c a a p p a a c c i i t t o o r r s s , , s s e e e e P P R R O O D D - - S S V V B B 0 0 6 6 * * - - E E N N . .
I I m m p p o o r r t t a a n n t t : : HIGH VOLTAGE IS PRESENT AT TERMINAL
BLOCK OR UNIT DISCONNECT SWITCH.
3. To modify parameters:
a. Press Main Menu twice (if TR150 drive) (press
Back if the main menu does not display)
b. Use the Up and Down buttons to find the
parameter menu group (first part of parameter
number)
c. Press OK
Table 77, p. 201
have
199