Table 44. GBAS voltage vs. setpoint (continued)
Setpoint
Unocc Zone Heating Setpoint
SA Cooling Setpoint (VAV only)
SA Cooling Setpoint (SZVAV only)
Zone Cooling Setpoint (SZVAV only)
Zone/Return Critical Temperature Setpoint (RR only)
SA Heating Setpoint (VAV only)
SA Heating Setpoint (SZVAV only)
Space Static Pressure Setpoint
SA Static Pressure Setpoint
Min OA Flow Setpoint 1
MWU Setpoint
Econ Dry Bulb Enable Setpoint
SA_Reheat_Setpoint
Minimum Position Setpoint 3
Occ Dehumidification Setpoint
Unocc Dehumidification Setpoint
Occ Humidification Setpoint
Unocc Humidification Setpoint
Notes:
1.
If DCV is enabled this is used for Design Minimum OA Flow Setpoint
2.
If DCV is enabled, this is used for Design Minimum OA Damper Position Setpoint
Table 45. GBAS 0-10 VDC output range
Setpoint
Outdoor Air Temperature
Zone Temperature
Supply Air Temperature (VAV only)
Supply Air Pressure (VAV only)
Space Pressure
Space RH
OA RH
Space CO
Level
2
Cooling Capacity %
Heating Capacity %
Outdoor Air Damper Position
Outdoor Airflow
RT-SVX24Q-EN
GBAS 0-5 VDC
GBAS 0-10 VDC
0.5 to 4.5 VDC
0.5 to 4.5 VDC
0.5 to 4.5 VDC
0.5 to 4.5 VDC
0.5 to 4.5 VDC
0.5 to 4.5 VDC
0.5 to 4.5 VDC
0.5 to 4.5 VDC
0.5 to 4.5 VDC
0.5 to 4.5 VDC
0.5 to 4.5 VDC
0.5 to 4.5 VDC
0.5 to 4.5 VDC
0.5 to 4.5 VDC
0.5 to 4.5 VDC
0.5 to 4.5 VDC
0.5 to 4.5 VDC
0.5 to 4.5 VDC
GBAS 0-10 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
Valid Range
0.5 to 9.5 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
-0.20 to 0.30 IWC
0.5 to 9.5 VDC
0.7 to 5.1 IWC
0.5 to 9.5 VDC
0 to Unit Max Flow
0.5 to 9.5 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
Valid Range
-40 to 200°F
-40 to 200°F
-40 to 200°F
0.0 to 7.91 wc
-0.67-0.67 wc
0-100%
0-100%
50-2000 PPM
0-100%
0-100%
0-100%
0 to 65,000 CFM
I I n n s s t t a a l l l l a a t t i i o o n n
50 to 90°F
40 to 90°F
40 to 70°F
50 to 80°F
75 to 95°F
40 to 180°F
65 to 95°F
50 to 90°F
50 to 140°F
60 to 90°F
0 to 100%
40 to 65%
40 to 65%
20 to 50%
20 to 50%