Information Messages - Swegon GOLD RX Manual

Generation f alarms and information messages

Advertisement

2. Information Messages

Information messages are displayed in the hand-held terminal.
Information messages are displayed only when the terminal is in
the Dashboard image.
Message No.
96:1
96:2
96:3
96:4
96:5
97:12
97:13
97:14
97:15
98:1
98:2
98:3
98:4
98:5
98:6
98:7
98:8
98:9
98:10
98:11
We reserve the right to alter specifications without notice.
Message text
HC DEFROSTING CALIBRATION NOT PERFORMED
HC defrosting calibration cannot be performed.
HC DEFROSTING CALIBRATION NOT APPROVED
HC defrosting calibration is performed, but read values are not approved.
HC LIMIT FOR SUPPLY AIR FLOW IS BELOW THE FACTORY SETTING
The set limit for the supply air flow is below the factory setting that permits HC operation.
HC LIMIT FOR EXTRACT AIR FLOW IS BELOW THE FACTORY SETTING
The set limit for the extract air flow is below the factory setting that permits HC operation.
HC OUTDOOR TEMPERATURE LIMIT FOR HEATING BELOW THE FACTORY SETTING
The set limit for the outdoor air temperature is below the factory setting that permits HC operation.
PLATE HEAT EXCHANGER, BYPASS OPTIMIZATION NOT PERFORMED
Bypass optimization of plate heat exchanger cannot be performed.
PLATE HEAT EXCHANGER, BYPASS OPTIMIZATION FAILURE
Bypass optimization of the plate heat exchanger has been performed, but the readings are not satisfactory.
PLATE HEAT EXCHANGER DEFROSTING CALIBRATION NOT PERFORMED
Defrosting calibration of the plate heat exchanger cannot be performed.
PLATE HEAT EXCHANGER DEFROSTING CALIBRATION FAILURE
Defrosting calibration of the plate heat exchanger has been performed, but the readings are not satisfactory.
SUPPLY AIR PRE-FILTER CALIBRATION NOT PERFORMED
Pre-filter calibration, supply air, not performed after first start. Recurrent at 30 minute intervals. The message is
not received after completed filter calibration.
SUPPLY AIR PRE-FILTER CALIBRATION FAILURE
Pre-filter calibration failure, supply air. Recurrent at 5 second intervals.
EXTRACT AIR PRE-FILTER CALIBRATION NOT PERFORMED
Pre-filter calibration, extract air, not performed after first start. Recurrent at 30 minute intervals. The message
is not received after completed filter calibration.
EXTRACT AIR PRE-FILTER CALIBRATION FAILURE
Pre-filter calibration failure, extract air. Recurrent at 5 second intervals.
SUPPLY AIR AHU FILTER CALIBRATION NOT PERFORMED
supply air AHU filter calibration, supply air, not performed after first start. Recurrent at 30 minute intervals.
The message is not received after completed filter calibration.
SUPPLY AIR AHU FILTER CALIBRATION FAILURE
AHU filter calibration failure, supply air. Recurrent at 5 second intervals.
EXTRACT AIR AHU FILTER CALIBRATION NOT PERFORMED
AHU filter calibration, extract air, not performed after first start. Recurrent at 30 minute intervals. The message
is not received after completed filter calibration.
EXTRACT AIR AHU FILTER CALIBRATION FAILURE
AHU filter calibration failure, extract air. Recurrent at 5 second intervals.
SUPPLY AIR END FILTER CALIBRATION NOT PERFORMED
End filter calibration, supply air, not performed after first start. Recurrent at 30 minute intervals. The message
is not received after completed filter calibration.
SUPPLY AIR END FILTER CALIBRATION FAILURE
End filter calibration failure, supply air. Recurrent at 5 second intervals.
ROTARY HEAT EXCHANGER DEFROSTING CALIBRATION NOT PERFORMED
Defrost calibration, rotary heat exchanger, not performed after function was activated for first time. Recurrent
at 30 minute intervals. The message is not received after completed heat exchanger calibration.
Information messages provide information e.g. about necessary
settings that have not been entered or unfavourable operating
conditions.The information message is indicated by a blue circle
in the alarm log button on the instrument panel.