Swegon GOLD RX Manual page 33

Generation f alarms and information messages

Advertisement

Alarm No.
Alarm text
Function
Alarm group 77 – 79: MIRU, motor controllers
77-
1142,
MIRU NO. 1-3 MOTOR CONTROLLER OVERCURRENT
79:2
1157,
Motor controller for roof ventilator MIRUVENT has regis-
1172
tered excessively high current to the drive motor.
77-
1143,
MIRU NO. 1-3 MOTOR CONTROLLER UNDERVOLTAGE
79:3
1158,
Low supply voltage to the roof ventilator MIRUVENT's
1173
motor controller.
77-
1144,
MIRU NO. 1-3 MOTOR CONTROLLER OVER VOLTAGE
79:4
1159,
High supply voltage to the roof ventilator MIRUVENT's
1174
motor controller.
77-
1145,
MIRU NO. 1-3 MOTOR CONTROLLER OVER TEMPERA-
79:5
1160,
TURE
1175
High internal temperature.
77-
1146,
MIRU NO. 1-3 MOTOR CONTROLLER START-UP FAILURE
79:6
1161,
Drive motor does not rotate during start up.
1176
77-
1147,
MIRU NO. 1-3 MOTOR CONTROLLER UNEVEN PHASE
79:7
1162,
VOLTAGE
1177
High voltage difference between the phases (3-phase,
400 V), which causes rippling.
77-
1148,
MIRU NO. 1-3 MOTOR CONTROLLER PHASE ERROR
79:8
1163,
Phase failure in motor controller.
1178
77-
1149,
MIRU NO. 1-3 MOTOR CONTROLLER INTERNAL
79:9
1164,
MEMORY ERROR
1179
Internal memory error in motor controller.
77-
1150,
MIRU NO. 1-3 MOTOR CONTROLLER CURRENT LIMITA-
79:10
1165,
TION
1180
Current/Voltage limitation in motor controller.
77-
1151,
MIRU NO. 1-3 MOTOR CONTROLLER INTERNAL COM-
79:11
1166,
MUNICATIONS ERROR
1181
Internal communication error in motor controller.
Alarm group 81 – 84: SMART Link, supply air flow
81-
1202,
SMART LINK NO. 1-4 SUPPLY AIR FLOW BELOW
84:2
1217,
DEFROSTING ALARM LIMIT
1232,
The alarm for supply air flow below defrosting alarm
1247
limit has tripped.
81-
1203,
SMART LINK NO. 1-4 HIGH PRESSURE MONITOR
84:3
1218,
TRIPPED
1233,
The high pressure monitor alarm has tripped.
1248
81-
1204,
SMART LINK NO. 1-4 HIGH PRESSURE ABOVE ALARM
84:4
1219,
LIMIT
1234,
The high pressure sensor measures higher pressure than
1249
preset alarm limit pressure.
81-
1205,
SMART LINK NO. 1-4 LOW PRESSURE BELOW ALARM
84:5
1220,
LIMIT
1235,
The low pressure sensor measures lower pressure than
1250
preset alarm limit pressure.
81-
1206,
SMART LINK NO. 1-4 EVAPORATION TEMPERATURE
84:6
1221,
BELOW ALARM LIMIT
1236,
The evaporation temperature drops below the preset
1251
alarm limit for more than 30 seconds.
We reserve the right to alter specifications without notice.
GB.GOLDSKFLARM.190920
Priority
Stop
0 = Blocked 0 = In oper. s = second
A = A alarm
1 = Stop
m = minute 1 = automatic
B = B alarm
h=hour
A
0
A
0
A
0
A
0
A
0
A
0
A
0
A
0
A
0
A
0
A
0
A
0
A
0
A
0
A
0
Delay
Resetting
0 = manual
10 s
0
60 sec.
0
10 s
0
10 s
0
10 s
0
10 s
1
10 s
1
10 s
1
60 sec.
1
10 s
1
70 m
1
30 s
1
30 s
1
30 s
1
30 s
1
www.swegon.com
33