Swegon GOLD RX Manual page 12

Generation f alarms and information messages

Advertisement

Alarm No.
Alarm text
Function
11:11
161
OUTDOOR TEMPERATURE SENSOR NO. C DEFECTIVE
Outdoor temperature sensor C is defective or is not con-
nected.
Check that the function selector switch on the room
sensor is set to position C and that the cable is con-
nected to COM 1-3 on the IQlogic controller.
For several connected sensors: check that the function
selector switches are not set in the same position and
check that the cables are connected correctly between
the sensor and connection unit. 10 second alarm delay.
11:12
162
OUTDOOR TEMPERATURE SENSOR NO. D DEFECTIVE
Outdoor temperature sensor D is defective or is not con-
nected.
Check that the function selector switch on the room
sensor is set to position D and that the cable is con-
nected to COM 1-3 on the IQlogic controller.
For several connected sensors: check that the function
selector switches are not set in the same position and
check that the cables are connected correctly between
the sensor and connection unit. 10 second alarm delay.
11:13
163
ROOM TEMPERATURE VIA COMMUNICATION, COM-
MUNICATION ERROR
The air handling unit's control unit does receive the
temperature via the external communications interface
within the set time limit.
5 minute alarm delay (adjustable).
11.14
164
Xzone, ROOM TEMPERATURE FROM COMMUNICATION
ERROR
The air handling unit's control unit does receive the
temperature via the external communications interface
within the set time limit.
5 minute alarm delay (adjustable).
11:15
165
OUTDOOR TEMPERATURE FROM COMMUNICATION
ERROR
The air handling unit's control unit does receive the
temperature via the external communications interface
within the set time limit.
5 minute alarm delay (adjustable).
Alarm group 12: AHU, temperature diff.
12:1
166
SUPPLY AIR TEMPERATURE BELOW SET POINT ALARM
LIMIT
The supply air temperature is below the preset setpoint
(ERS, ORS and supply air regulation) or has deviated
from the supply air regulator's current setpoint (for
extract air regulation) longer than 20 minutes.
Alarm limit 5 K (adjustable).
Check the correct function on heat exchangers and
any reheaters. Also check that the aforementioned are
dimensioned for the current setpoint.
12
www.swegon.com
GB.GOLDSKFLARM.190920
Priority
Stop
0 = Blocked 0 = In oper. s = second
A = A alarm
1 = Stop
m = minute 1 = automatic
B = B alarm
h=hour
B
0
3)
B
0
3)
B
0
3)
B
0
3)
B
0
3)
A
1
3)
We reserve the right to alter specifications without notice.
Delay
Resetting
0 = manual
10 s
1
10 s
1
5 m
2)
1
5 m
1
2)
5 m
1
2)
20 m