Generation f alarms and information messages

Advertisement

Alarm No.
Alarm text
Function
Alarm group 8: Cooling
8:5
110
COOLING, VALVE MONITORING TRIPPED
Valve actuator, air cooler.
The valve actuator's response signal deviates from the
outgoing control signal.
10 minute alarm delay.
8:6
111
COOLING ALARM INPUT 1 TRIPPED
Alarm input 1 cooling has tripped.
The alarm input is selected on one of the I/O-modules
No 3 or 6 digital inputs. Check terminal connections 17-
18 or terminal connections 19-20.
20 second alarm delay.
8:7
112
COOLING ALARM INPUT 2 TRIPPED
Alarm input 2 cooling has tripped.
The alarm input is selected on one of the I/O-modules
No 3 or 6 digital inputs. Check terminal connections 17-
18 or terminal connections 19-20.
20 second alarm delay.
Alarm group 9: Spare
Alarm group 10: AHU, internal temperature sensor
10:1
136
SUPPLY AIR TEMPERATURE SENSOR DEFECTIVE
Supply air sensor is defective or is not connected.
Check that the sensor is connected to the connection
marked "SA Temp" on the IQlogic controller.
3 second alarm delay.
10:2
137
SUPPLY AIR TEMPERATURE SENSOR FOR DENSITY COM-
PENSATION DEFECTIVE
Supply air sensor in the supply air fan intake cannot
establish correct communications or shows an incorrect
value.
Check that the sensor is connected to the connection
on the IQlogic controller. Depending on the air direc-
tion, the sensor is connected to the connection marked
"Sensor 3" (the sensor placed on the left-hand side) or
"Sensor 4" (the sensor placed on the right-hand side).
For GOLD RX the sensor can also be used as a tem-
perature alarm and be placed after the supply air fan. 3
second alarm delay.
10:3
138
EXTRACT AIR TEMPERATURE SENSOR DEFECTIVE
Extract air sensor is defective or is not connected.
Check that the sensor is connected to the connection
on the IQlogic controller. Depending on the air direc-
tion, the sensor is connected to the connection marked
"Sensor 1" (the sensor placed on the left-hand side) or
"Sensor 2" (the sensor placed on the right-hand side). 3
second alarm delay.
8
www.swegon.com
GB.GOLDSKFLARM.190920
Priority
Stop
0 = Blocked 0 = In oper. s = second
A = A alarm
1 = Stop
m = minute 1 = automatic
B = B alarm
h=hour
B
0
3)
A
0
A
0
A
1
3)
B
0
3)
A
1
3)
We reserve the right to alter specifications without notice.
Delay
Resetting
0 = manual
10 s
0
20 s
0
20 s
0
3 s
1
3 s
1
3 s
1