Generation f alarms and information messages

Advertisement

Alarm No.
Alarm text
Function
13:3
184
EXTRACT AIR HUMIDITY SENSOR DEFECTIVE
The humidity sensor in the extract air duct is defective
or is not connected.
Check that the cable is connected to COM 1-3 on the
IQlogic controller.
10 second alarm delay.
13:4
184
EXHAUST AIR HUMIDITY SENSOR DEFECTIVE
The humidity sensor in the exhaust air duct is defective
or is not connected.
Check that the cable is connected to COM 1-3 on the
IQlogic controller.
10 second alarm delay.
13:9
189
HUMIDIFIER, ALARM OUTPUT TRIPPED
The humidifier has tripped alarm output.
Check terminal connections 11-12 on I/O-module with
the function selector switch in position 4. Check that
the alarm setting corresponds with the current function
(making, breaking, contactor function).
10 second alarm delay.
13:11
191
VOC SENSOR COMMUNICATION ERROR
The air handling unit's control unit cannot establish cor-
rect communications with the VOC sensor.
Check that the cable is connected to COM 1-3 on the
IQlogic controller. Check the polarity of any extension
cables.
10 second alarm delay.
13:12
192
VOC SENSOR, INTERNAL COMMUNICATION ERROR
The air handling unit's control unit cannot achieve cor-
rect communications with the VOC sensor.
Check that the cable is connected to COM 1-3 on the
IQlogic controller. The internal communications in the
sensor does not work. Replace the sensor.
60 second alarm delay.
13:13
193
VOC SENSOR, INTERNAL ERROR
VOC sensor defective.
Check that the cable is connected to COM 1-3 on the
IQlogic controller. Measuring element in the sensor has
failed. Replace the sensor.
60 second alarm delay.
13:14
194
VOC SENSOR, LEVEL BELOW/ABOVE SET POINT ALARM
LIMIT
The VOC sensor has read a level below or above the set
point alarm limit for more than 60 seconds.
Factory setting 450 ppm and 10,000 ppm (adjustable).
Alarm group 14: Spare
14
www.swegon.com
GB.GOLDSKFLARM.190920
Priority
Stop
0 = Blocked 0 = In oper. s = second
A = A alarm
1 = Stop
m = minute 1 = automatic
B = B alarm
h=hour
A
0
3)
A
0
3)
A
0
3)
B
0
3)
B
0
3)
B
0
3)
B
0
3)
We reserve the right to alter specifications without notice.
Delay
Resetting
0 = manual
10 s
1
10 sec.
1
10 s
0
10 s
1
60 s
1
60 s
1
60 s
1

Advertisement

loading

This manual is also suitable for:

Gold pxGold cxGold sd