GB.GOLDLP.170830 Operation and Maintenance Instructions GOLD LP Applicable to program version 3.04 and newer versions The document was originally written in Swedish. www.swegon.com We reserve the right to alter specifications without notice.
DThe type RECOnomic rotary heat exchanger is variable speed controlled and has a peak temperature efficiency of In order to fully obtain all the benefits the GOLD LP has to 85%. offer, it is important keep in mind the air handling unit’s...
19 Mounting bracket for securing the unit in position, 4 6 Hand-held Micro Terminal brackets 7 Main switch/Safety switch 20 Supply air filter* 8 Extract air filter* 21 Slide rails for the inspection panels www.swegon.com We reserve the right to alter specifications without notice.
2.1 Safety Isolating Switch/Main Switch cover of the electrical equipment cubicle must be fastened while the air handling unit is operating. On the GOLD LP one-piece unit, the safety isolating switch is externally positioned on the electrical equipment cubi- cle.
(AIR ADJUSTMENT menu). Adjust the ducting system and air devices as described in Section 4.2. 6. Finish off with a filter calibration as described in Section 7.4.2. www.swegon.com We reserve the right to alter specifications without notice.
Check that all dampers have the same ratio. When the adjustment has been completed, 3 air devices and one branch damper should stand fully open to obtain the lowest K (Ratio) = possible pressure in the system. www.swegon.com We reserve the right to alter specifications without notice.
20 Pa greater will deviate from the preset extract airflow. The devia- than the negative pressure in the supply air section tion increases as the difference in pressure increases. (0–20 Pa). www.swegon.com We reserve the right to alter specifications without notice.
GB.GOLDLP.170830 HAND-HELD MICRO TERMINAL AND HOW TO USE THE MENUS GOLD LP TUE 14:40 5.1 HAND-HELD MICRO TERMINAL STOP MANUAL OPERATION 5.1.1 General STOP? The hand-held micro terminal consists of an encapsulated control box with a 3-metre long cable for connection to the air handling unit by means of a quick connector.
GB.GOLDLP.170830 5.2 Menu tree Important! The appearance of GOLD LP TUE 14:40 STOP the menus varies depending MANUAL OPERATION on the type of air handling STOP? unit and functions selected. MAIN GOLD LP TUE 14:40 MANUAL OPERATION MENU STOP? MAN/AUTO.OP...
GB.GOLDLP.170830 MAIN MENU GOLD LP TUE14:40 STOP MANUAL OPERATION 6.1 General STOP? The main menu is normally shown if no other menu GOLD LP TUE14:40 has been selected. MANUAL OPERATION STOP? The display automatically returns to the main menu MAN/AUTO.OP after 30 minutes.
Min. supply air temperature 13-25 °C* 15 °C Max. supply air temperature 18-45 °C* 28 °C *) The setting range can be changed. See 14.3, Min/Max Adjustment. X = Extract air temperature °C www.swegon.com We reserve the right to alter specifications without notice.
This means that the fans will not operate outside these limits, regardless the load. Min/Max Airflows AIRFLOW MIN. FLOW MAX. FLOW GOLD LP GOLD LP /h * SIZE 0.08 1900 0.53 0.20 2600 0.74...
When calibration R-HX is activated the fans are accelerated to eventual adjustment plates have been fitted and adjusted; after high speed for about 3 minutes. that every time the filter media are changed. www.swegon.com We reserve the right to alter specifications without notice.
ALARM HISTORY The 10 most recent tripped alarms are shown. Alarm settings can be entered at INSTALLATION LEVEL under ALARM SETTINGS. For complete description of alarms, see Section 18. www.swegon.com We reserve the right to alter specifications without notice.
EXTERNAL ALARMS ALARM LIMITS ALARM PRIORITY *HAND TERMINAL INST* Section 14 LANGUAGE AIR FLOW UNIT MIN/MAX SETTING BASE SETTINGS *COMMUNICATION* Section 15 EIA-485 ETHERNET *SERVICE LEV.* Section 16 CODE: 0000 www.swegon.com We reserve the right to alter specifications without notice.
1. The temperature efficiency of the air handling unit’s heat exchanger is modulated to provide max. heat recovery. 2. After that, the re-heating coil, if installed, will begin to generate heat. www.swegon.com We reserve the right to alter specifications without notice.
18 °C (Y2). functions can also affect the preset temperatures. If the extract air temperature is above 22 °C (X3), the supply air temperature setpoint will be constantly 14 °C (Y3). www.swegon.com We reserve the right to alter specifications without notice.
15 °C Max. Supply air temperature 25-45 °C 28 °C Setting range for the various values is limited by Min. and Max. settings at INSTALLATION LEVEL under HAND TERMI- NAL. www.swegon.com We reserve the right to alter specifications without notice.
0–2 °C up to outdoor temperature +40 °C. Outdoor temperature +40 °C (Breakpoint X4): Constant compensation takes place with 2 °C (temperature displa- cement Y2). www.swegon.com We reserve the right to alter specifications without notice.
Extract air temperature for stop 12 - 22 °C 16 °C Outdoor temperature for stop 5 - 15 °C 10 °C Supply air setpoint 10 - 20 °C 10 °C Operating period 00:00-00:00 23:00-06:00 www.swegon.com We reserve the right to alter specifications without notice.
HEATING ity of the function will be best if the GOLD is provided with INTERM. NIGHT HEAT COOLING a recirculation damper (not Swegon supply) and a shut-off MORNING BOOST HUMIDITY damper for outdoor air and exhaust air. SETPOINT TEMP DISPL IN/OUTPUTS EXT.
Value Setting Factory range setting When the function is activated, the setpoint is offset as Setpoint temp displacement Inactive/active Inactive illustrated in the chart to the right. www.swegon.com We reserve the right to alter specifications without notice.
As an alternative, a temperature reading can be commu- nicated to the air handling via communication from e.g. a main system. The alarm setting indicates how long the alarm will be delayed if communication is lost. www.swegon.com We reserve the right to alter specifications without notice.
Both fans cannot be controlled as slaves. If both are selec- ted by mistake, the extract air fan will be forced to operate in the flow regulation mode. www.swegon.com We reserve the right to alter specifications without notice.
0–30 % down to outdoor air temperature -20 °C. Outdoor air temperature -20 °C (Breakpoint X1): Constant compensation proceeds at 30 % (max reduction Y1). www.swegon.com We reserve the right to alter specifications without notice.
TEMPERATURE Settings: AIR FLOW/PRESSURE Value Setting Factory FILTER range settings OPERATION Standard filter Inactive/SA/EA SA+EA HEATING SA+EA COOLING Prefilter Inactive/SA/EA SA+EA HUMIDITY SA+EA IN/OUTPUTS IQnomic Plus ALL YEAR COMFORT OPTIMIZE www.swegon.com We reserve the right to alter specifications without notice.
March and the last Sunday in October respectively). This automatic changeover can be blocked and set as inac- tive. Settings: Value Setting Factory range settings Summer time/Winter time Inactive/active Active www.swegon.com We reserve the right to alter specifications without notice.
Note that the heat exchanger performs less efficiently while defrosting is in progress and that the supply air tem- perature will decrease downstream of the heat exchanger. Settings: Value Setting Factory range settings Defrosting Inactive/active Inactive www.swegon.com We reserve the right to alter specifications without notice.
For particulars on setting the max. flow, see Section 7.2. Settings: Value Setting Factory range settings Heating BOOST Inactive/active Inactive Start limit 2-10 °C 3 °C Ramp time 0.5-15% 2.5% www.swegon.com We reserve the right to alter specifications without notice.
0-100 % cooling demand and can be used for indicating the cooling min supply air temp 2-10 °C 3 °C demand, for instance. Connect to the IQnomic Plus module, termi- Ramp time 0.5-15% 2.5% nals 15-16. www.swegon.com We reserve the right to alter specifications without notice.
If the conditions for outdoor air are not met, the unit will the premises. begin increasing the airflow when the cooling unit starts Cooling BOOST cannot be combined with pressure regu- www.swegon.com We reserve the right to alter specifications without notice.
Settings: Value Setting Factory range settings Dehumidification Inactive/active Inactive Supply air – rel. humidity (%RH) 10-90% Example of dehumidification control Temp. sensor, supply air Moisture sensor, TBLZ-1-31-1 www.swegon.com We reserve the right to alter specifications without notice.
– External Alarm 2: For connection of External Alarm 2. – External reset: For connection of pushbutton for reset- ting a tripped alarm. External fire alarm: A fire alarm will trip if the input is not connected. www.swegon.com We reserve the right to alter specifications without notice.
IQnomic Plus is a name given to additional modules for extra control functions. FUNCTIONS See special instructions. *FUNCTIONS* TEMPERATURE AIR FLOW/PRESSURE FILTER OPERATION HEATING COOLING HUMIDITY IN/OUTPUTS IQnomic Plus *IQNOMIC PLUS* ALL YEAR COMFORT OPTIMIZE www.swegon.com We reserve the right to alter specifications without notice.
1-60 min Night comp., Cooling water Active Inactive Interval (h) 1-168 h Inactive Dew point comp. Active Inactive Temp. comp. (°C) -10-+10 °C Inactive Neutral zone(°C) 0-5°C Comp. flow (%) 0-30% www.swegon.com We reserve the right to alter specifications without notice.
The OPTIMIZE function optimizes the GOLD unit’s airflow rates for the connected WISE system. See the special FUNCTIONS documentation for WISE. *FUNCTIONS* TEMPERATURE AIR FLOW/PRESSURE FILTER OPERATION HEATING COOLING HUMIDITY IN/OUTPUTS IQnomic Plus ALL YEAR COMFORT OPTIMIZE www.swegon.com We reserve the right to alter specifications without notice.
The anti frost monitoring function is always active if the air heater for hot water connected has been supplied by The GOLD has a number of automatic functions. The Swegon. operation of the unit is influenced when certain functions are activated.
On a return to the other menu groups, the controller resu- mes normal operation and all settings for manual testing will be terminated. Each menu indicates which functions can be test run. www.swegon.com We reserve the right to alter specifications without notice.
The priority of certain alarms cannot be changed. Value Setting Factory range settings Settings: Time delay 1-600 sec 10 sec See 18.2 Alarm Descriptions. Alarm at closure 1=closure 0=disconnection Alarm reset 0=auto/1=man 0 www.swegon.com We reserve the right to alter specifications without notice.
Load new setting 1 Load new setting 2 ERS= Extract air temperature-related supply air temperature-re- external memory Fetch setting 1 gulation Fetch setting 2 Fetch current setting Fetch all Factory setting Activate www.swegon.com We reserve the right to alter specifications without notice.
Communication can also be established via Ether- net without software other than an ordinary web browser such as Internet Explorer. Further information about interfaces, proto- cols and configuration is available at www. swegon.com. 15.1 EIA-485 Protocol and settings for EIA-485 is specified. Settings: Value...
If needed, the heat exchanger can be withdrawn from Order new filters from Swegon or your nearest Swegon the unit casing and washed with degreasing solvent. Only representative. State the type of air handling unit, and...
Alarms that reset themselves automatically do so as soon as the fault has been remedied. Alarms can also be reset via a communication network. 18.1.3 Changing Alarm Settings See Section: 13 Alarm Settings. www.swegon.com We reserve the right to alter specifications without notice.
** Not adjustable, stops the air handling unit if the temperature to below +5 ºC. *** Blocked if the hand terminal does not display the main menu. **** Cannot be blocked. www.swegon.com We reserve the right to alter specifications without notice.
The heat exchanger’s defrosting function has operated for the full max period 6 times during one 24-hour period. *** Blocked if the hand terminal does not display the main menu. www.swegon.com We reserve the right to alter specifications without notice.
7 days. A new service period can be set in the ALARM SET- TINGS menu. *** Blocked if the hand terminal does not display the main menu. www.swegon.com We reserve the right to alter specifications without notice.
Broken signal is obtained at DI2 for I/0-module 6. The motor protection or pressure switch may have tripped. *** Blocked if the hand terminal does not display the main menu. www.swegon.com We reserve the right to alter specifications without notice.
– – – –**** TIME LOCK TRIPPED Contact Swegon or their representative. B*** 10 m COOLING VALVE I/O-7 DEFECTIVE Controls of the Cooling valve do not obtain the same signal on AI 1 as on AU1 on I/O-module.
The VOC sensor has read a level below or above the set point alarm limit for more than 60 seconds. *** Blocked if the hand terminal does not display the main menu. www.swegon.com We reserve the right to alter specifications without notice.
The pressure across the prefilters was not calibrated after the first start. Recurrent at 24-hour intervals. The message will not be received after the pressure across the prefilters has been calibrated. www.swegon.com We reserve the right to alter specifications without notice.
GB.GOLDLP.170830 TECHNICAL DATA 20.1 Dimensions, GOLD LP one-piece unit Clear service space Electrical equipment cubicle A clear space of 500 mm open space must be provided in front of inspection panels on the inspection side or in front of the extra inspection panel on the long sides for changing the filters.
The electrical equipment cubicle contains two units: the control unit and the power unit. The GOLD LP control unit and the power unit are located inside the electrical equipment cubicle. For access, remove the cover of the electrical equipment cubicle.
GOLD LP, right-hand version: DIL switch 6 must be set to the ON position, the other switches must be set to the OFF position. GOLD LP, left-hand version: DIL switches 1 and 6 must be set to the ON position, the other switches must be set to the OFF position.
Step motor, 3-phase, 5.8 A (2A)*, 50 V max 90 V. *) The motor controls limit the output power to the value speci- fied. 20.3.5 Control Inaccuracy Temperature ± 1 Airflow ± 5%. www.swegon.com We reserve the right to alter specifications without notice.
Box 300 SE-535 23 Kvänum, Sweden This declaration is applicable only if the air handling unit(s) has/have been installed according to Swegon’s instructions and provided that the air handling unit(s) has/have not been modified in any way. Kvänum, 01/28/2011 Thord Gustafsson, Quality and Environmental Manager, Swegon AB www.swegon.com...
– – Inactive Stop High – – – – Inactive Stop High – – – – Inactive Stop High – – – – Inactive Stop High – – – – www.swegon.com We reserve the right to alter specifications without notice.
SA max 28.0°C Set point displacement X Inactive Active Inactive Active External sensor External EA/Room X Inactive IQnom Comm. Inactive IQnom Comm. External outdoor X Inactive IQnom Comm. Inactive IQnom Comm. www.swegon.com We reserve the right to alter specifications without notice.
Inact. X SA+EA Inact. SA+EA Prefilter X Inact. SA+EA Inact. SA+EA Extended operation External low speed (h:mm) 0:00 External low speed (h:mm) 0:00 * Not used for Clean Air Control www.swegon.com We reserve the right to alter specifications without notice.
I/O Module No. 3 Ext. monitoring X Inactive Active Inactive Active I/O Module No. 6 Ext. cooling X Inactive Active Inactive Active I/O Module No. 9 Preheating X Inactive Active Inactive Active www.swegon.com We reserve the right to alter specifications without notice.
Exercising, Cooling water X Inact. Pump Valvev Inact. Pump Valve Exercising period, (min) Interval (h) Dew point comp. X Inact. Active Inact. Active Neutral zone (°C) Comp. air flow (%) www.swegon.com We reserve the right to alter specifications without notice.
I/O module Nr 9 Preheating Inactive Active Inactive Active I/O module Nr A Heating zone Inactive Active Inactive Active I/O module Nr B Cooling zone Inactive Active Inactive Active www.swegon.com We reserve the right to alter specifications without notice.
Break point, ERS Regulation (°C) 15,0/23,0 SA/EA Difference (°C) 1,0/5,0 Initial setting – Communication EIA-485 Protocol Modbus RTU Address PLA (Exoline) 1 ELA (Exoline) 1 Speed 9600 Parity None Stop bit www.swegon.com We reserve the right to alter specifications without notice.
A, group alarm B, control of external heating, control of external cooling. 7) Possible options: External stop, external low speed operation, external high speed operation, external alarm 1, external alarm 2, external reset, external heating, external fire alarm. www.swegon.com We reserve the right to alter specifications without notice.
R.hx pressure drop above alarm limit B *** El.heating coil tripped A *** Extract air temp below alarm limit A *** Supply air temp below setpoint A *** Ext.alarm No.1 tripped A*** www.swegon.com We reserve the right to alter specifications without notice.
Extract air humidity sensor faulty A *** Supply air, prefilter fouled. B*** Exhaust air prefilter, fouled B*** Cooling Output 1 tripped Cooling Output 2 tripped No comm. with press. sensor by SA prefilter B*** www.swegon.com We reserve the right to alter specifications without notice.
** Not adjustable, stops the air handling unit at temperature below +5 °C *** Blocked if the hand terminal does not display the main menu. **** Cannot be blocked. Adjustments carried out by: Date Company Name www.swegon.com We reserve the right to alter specifications without notice.
GB.GOLDLP.170830 All documentation is available in digital form and can be downloaded from www.swegon.com www.swegon.com We reserve the right to alter specifications without notice.