Swegon GOLD RX Manual page 9

Generation f alarms and information messages

Advertisement

Alarm No.
Alarm text
Function
10:4
139
EXTRACT AIR TEMPERATURE SENSOR FOR DENSITY
COMPENSATION DEFECTIVE (GOLD RX/PX/CX)
The temperature sensor in the extract air fan intake
cannot establish correct communications or shows an
incorrect value.
Check that the sensor is connected to the connection
on the IQlogic controller. Depending on the air direc-
tion, the sensor is connected to the connection marked
"Sensor 3" (the sensor placed on the right-hand side) or
"Sensor 4" (the sensor placed on the left-hand side). 3
second alarm delay.
GOLD RX
Exhaust air regulation has been selected, but the tem-
perature sensor in the exhaust air is defective or is not
connected.
10:5
140
EXTRACT AIR TEMPERATURE SENSOR FOR HEAT EX-
CHANGER DEFROSTING DEFECTIVE
Temperature sensor, for heat exchanger defrosting is
defective.
Check that the sensor is connected to COM 6-11 on the
IQlogic controller. 10 second alarm delay.
10:6
141
EXTRACT AIR TEMPERATURE SENSOR FOR DENSITY
COMPENSATION IN SD AIR HANDLING UNIT DEFECTIVE
The temperature sensor in the extract air fan intake
cannot establish correct communications or shows an
incorrect value.
Check that the sensor (connected via a cable adapter)
is connected correctly to COM 6-11 on the IQlogic con-
troller. Also check the correct connection of the cable
between the cable adapter. 10 second alarm delay.
10:7
142
EXTRACT AIR DUCT TEMPERATURE SENSOR DEFECTIVE
External temperature sensor in the extract air duct is
defective or is not connected.
Check that the sensor is connected to COM 1-3 on the
IQlogic controller. 10 second alarm delay.
10:10
145
OUTDOOR AIR TEMPERATURE SENSOR DEFECTIVE
(GOLD SD)
Outdoor temperature sensor is defective or is not con-
nected.
Check that the sensor is connected to the connection
on the IQlogic controller. Depending on the air direc-
tion, the sensor is connected to the connection marked
"Sensor 1" (the sensor placed on the right-hand side) or
"Sensor 2" (the sensor placed on the left-hand side). 3
second alarm delay.
We reserve the right to alter specifications without notice.
GB.GOLDSKFLARM.190920
Priority
Stop
0 = Blocked 0 = In oper. s = second
A = A alarm
1 = Stop
m = minute 1 = automatic
B = B alarm
h=hour
B
0
3)
A
1
3)
A
1
3)
A
1
3)
B
0
3)
Delay
Resetting
0 = manual
3 s
1
10 s
1
10 s
1
10 s
1
3 s
1