Communication Error - Swegon GOLD RX Manual

Generation f alarms and information messages

Advertisement

Alarm No.
Alarm text
Function
Alarm group 24: SMART Link DX
24:1
346
SMART Link, no. 1 communication error
The air handling unit's control unit cannot establish cor-
rect communication with the chiller/heat pump 1.
24:2
347
SMART Link, no. 1 alarm tripped
Chiller 1 defective.
24:4
349
SMART Link, no. 2 communication error
The air handling unit's control unit cannot establish cor-
rect communication with the chiller/heat pump 2.
24:5
350
SMART Link, no. 2 alarm tripped
Chiller 2 defective.
24:7
352
SMART Link, no. 3 communication error
The air handling unit's control unit cannot establish cor-
rect communication with the chiller/heat pump 3.
24:8
353
SMART Link, no. 3 alarm tripped
Chiller 3 defective.
24:10
355
SMART Link, no. 4 communication error
The air handling unit's control unit cannot establish cor-
rect communication with the chiller/heat pump 4.
24:11
356
SMART Link, no. 4 alarm tripped
Chiller 4 defective.
24:13
358
SMART Link, supply air alarm flow below alarm limit
The alarm supply air flow below alarm limit has tripped.
Alarm group 24-25: Spare
Alarm group 26: Pre-filter
26:1
376
PRE-FILTER, SUPPLY AIR PRESSURE SENSOR NO. 8 COM-
MUNICATION ERROR
The air handling unit's control unit cannot establish
correct communication with the sensor of the supply air
pre-filter.
26:2
377
PRE-FILTER, SUPPLY AIR FOULED
The pressure across the supply air pre-filter exceeds the
preset alarm limit for more than 10 minutes.
26:7
382
PRE-FILTER, EXTRACT AIR PRESSURE SENSOR NO. 9

COMMUNICATION ERROR

The air handling unit's control unit cannot establish
correct communication with the sensor of the extract air
pre-filter.
26:8
383
PRE-FILTER, EXTRACT AIR FOULED
The pressure across the extract air pre-filter exceeds the
preset alarm limit for more than 10 minutes.
Alarm group 27: AHU, internal filters
27:1
391
AHU FILTER, SUPPLY AIR PRESSURE SENSOR NO. 3/4
COMMUNICATION ERROR
The air handling unit's control unit cannot establish cor-
rect communication with the sensor of the AHU supply
air filter.
27:2
392
AHU FILTER, SUPPLY AIR FOULED
The pressure across the AHU supply air filter has ex-
ceeded the preset alarm limit for more than 10 minutes.
24
www.swegon.com
GB.GOLDSKFLARM.190920
Priority
Stop
0 = Blocked 0 = In oper. s = second
A = A alarm
1 = Stop
m = minute 1 = automatic
B = B alarm
h=hour
A
0
3)
A
0
3)
A
0
3)
A
0
3)
A
0
3)
A
0
3)
A
0
3)
A
0
3)
A
0
B
0
3)
B
0
3)
B
0
3)
B
0
3)
B
0
3)
B
0
3)
We reserve the right to alter specifications without notice.
Delay
Resetting
0 = manual
30 s
1
30 s
1
30 s
1
30 s
1
30 s
1
30 s
1
30 s
1
30 s
1
10 m
1
10 s
1
10 m
0
10 s
1
10 m
0
10 s
1
10 m
0