Generation f alarms and information messages

Advertisement

Alarm No.
Alarm text
Function
38-
564, 579,
MIRU NO. 1-3 FLOW ABOVE SET POINT ALARM LIMIT
40:9
594
The flow has exceeded its set point by more that 10%,
during a longer period than 20 minutes.
38-
565, 580,
MIRU NO. 1-3 PRESSURE BELOW SET POINT ALARM
40:10
595
LIMIT
The pressure has dropped below its set point for a
period longer than 30 seconds.
38-
566, 581,
MIRU NO. 1-3 PRESSURE ABOVE SET POINT ALARM
40:11
596
LIMIT
The pressure has exceeded its set point by more that
10%, during a longer period than 20 minutes.
Alarm group 49-54: Supply air fan no. 1A-3B
49-
721, 736,
SUPPLY AIR FAN 1-3/A-B COMMUNICATION ERROR
54:1
751, 766,
The air handling unit's control unit cannot establish
781, 796
correct communication with the supply air fan motor
controller.
49-
722, 737,
SUPPLY AIR FAN 1-3/A-B MOTOR CONTROLLER OVERCUR-
54:2
752, 767,
RENT
782, 797
High current supplied to motor
49-
723, 738,
SUPPLY AIR FAN 1-3/A-B MOTOR CONTROLLER UNDER-
54:3
753, 768,
VOLTAGE
783, 798
Voltage below the normal level is supplied.
49-
724, 739,
SUPPLY AIR FAN 1-3/A-B MOTOR CONTROLLER OVER-
54:4
754, 769,
VOLTAGE
784, 799
Excessively high voltage is supplied.
49-
725, 740,
SUPPLY AIR FAN 1-3/A-B MOTOR CONTROLLER EXCESS
54:5
755, 770,
TEMPERATURE
785, 800
High internal temperature.
49-
726, 741,
SUPPLY AIR FAN 1-3/A-B MOTOR CONTROL START UP
54:6
756, 771,
ERROR
786, 801
Supply air fan does not rotate on a start up, rotates in
wrong direction or rotates at excessively high speed.
49-
727, 742,
SUPPLY AIR FAN 1-3/A-B MOTOR CONTROLLER UNEVEN
54:7
757, 772,
PHASE VOLTAGE
787, 802
High voltage difference between the phases (3-phase,
400 V), which causes rippling.
49-
728, 743,
SUPPLY AIR FAN 1-3/A-B MOTOR CONTROLLER PHASE
54:8
758, 773,
FAILURE
788, 803
Phase failure in motor controller.
49-
729, 744,
SUPPLY AIR FAN 1-3/A-B MOTOR CONTROLLER
54:9
759, 774,
MEMORY ERROR
789, 804
Internal memory error in motor controller.
49-
730, 745,
SUPPLY AIR FAN 1-3/A-B MOTOR CONTROLLER CUR-
54:10
760, 775,
RENT LIMITATION
790, 805
Current/Voltage limitation in motor controller.
49-
731, 746,
SUPPLY AIR FAN 1A-3A MOTOR CONTROLLER INTER-
51:11
761
NAL COMMUNICATION ERROR
Internal communication error in motor controller.
Alarm group 55-60: Extract air fan no. 1A-3B
55-
811, 826,
EXTRACT AIR FAN 1-3/A-B COMMUNICATION ERROR
60:1
841, 856,
The air handling unit's control unit cannot establish
871, 886
correct communication with the extract air fan motor
controller.
We reserve the right to alter specifications without notice.
8)
9)
GB.GOLDSKFLARM.190920
Priority
Stop
0 = Blocked 0 = In oper. s = second
A = A alarm
1 = Stop
m = minute 1 = automatic
B = B alarm
h=hour
B
0
B
0
B
0
A
1
3)
A
1
1)
3)
A
1
1)
3)
A
1
1)
3)
A
1)
1
3)
A
1
1)
3)
A
1)
1
3)
A
1
1)
3)
A
1)
1
3)
B
0
3)
A
1
3)
A
1
3)
Delay
Resetting
0 = manual
1200 s
0
1200 s
0
1200 s
0
10 s
1
10 s
0
60 s
0
10 s
0
10 s
0
10 s
0
10 s
1
10 s
1
10 s
1
60 s
1
10 s
1
10 s
1
www.swegon.com
29

Advertisement

loading

This manual is also suitable for:

Gold pxGold cxGold sd