Typical Configurations - Huawei UPS5000-E Series User Manual

25 kva power modules
Hide thumbs Also See for UPS5000-E Series:
Table of Contents

Advertisement

UPS5000-E-(25 kVA-125 kVA)
User Manual (25 kVA power modules)
Figure 2-17
Figure 2-17 RS485 pins
Table 2-8 RS485 pin definition

2.5 Typical configurations

Table 2-9
Issue 06 (2020-01-10)
and
Table 2-8
Pin
1
2
3
4
5
6
7
8
If cables are prepared onsite, follow the three methods below:
Connect pin 1 and pin 2. Pin 1 connects to RS485+ and pin 2 connects to RS485–.
Connect pin 4 and pin 5. Pin 4 connects to RS485+ and pin 5 connects to RS485–.
Connect pins 1, 2, 4, and 5. Twist cables to pin 1 and pin 4 into one cable and then connect it to
RS485+. Twist cables to pin 2 and pin 5 into one cable and then connect it to RS485–.
describes typical UPS configurations.
Copyright © Huawei Technologies Co., Ltd.
describe the RS485 pin definitions.
Description
RS485_T+
RS485_T–
N/A
RS485_R+
RS485_R–
GND
N/A
N/A
2 Overview
32

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ups5000-e-125k-f125

Table of Contents