5.6.3 Capacity Test

Context
Before a capacity test, ensure that:
Procedure
Step 1 On the main screen of the LCD, tap System Info.. Tap
displayed.
Step 2 (Optional) If you have not logged in, enter a user name and a password, and then tap
Step 3 On the Maintenance screen, tap Battery Maint., as shown in
Step 4 Tap Start on the right of Capacity Test to start a capacity test, as shown in
Issue 06 (2020-01-10)
The load ratio fluctuation exceeds 10%.
An alarm is generated.
The UPS is working in normal mode; float charging or hibernation has lasted for 2 hours
after the state of charge (SOC) reaches 100%; and the load ratio change rate less than 10%.
The UPS has generated no battery overtemperature, overvoltage, or overcurrent alarm. No
generator is connected to the UPS.
The mains, batteries, charger, and discharger are normal. No overload alarm is generated.
Table 4-4
lists the default user names and preset passwords and describes the permission of the
default users.
If you enter incorrect passwords for three consecutive times, you will be locked out for 5 minutes.