Huawei UPS5000-E Series User Manual page 171

25 kva power modules
Hide thumbs Also See for UPS5000-E Series:
Table of Contents

Advertisement

UPS5000-E-(25 kVA-125 kVA)
User Manual (25 kVA power modules)
Figure 5-48 Intelligent power parameters on the LCD
Set the preceding three parameters when you connect the D.G. to the UPS.
Step 4 After you set Intelligent power to Enable, the system changes some parameter values
associated with intelligent power.
values on the LCD.
Issue 06 (2020-01-10)
Intelligent power
The value can be Enable or Disable. The intelligent power function is available only if
the value is Enable. The default value is Disable.
ATS
The value can be Connected or Not connected. When the value is Connected, the UPS
works in the ATS scenario; when the value is Not connected, the UPS works in the reuse
scenario. The default value is Connected. This parameter is available only after you set
Intelligent power to Enable.
D.G. startup batt. volt. (V/cell)
The value ranges from 1.80 to 2.00. The default value is 1.80. This parameter is available
only after you set Intelligent power to Enable.