Figure 5-24 Automatic shallow discharge settings
----End
Manual Shallow Discharge Test
Step 1 On the home screen of the LCD, choose System Info and tap
Maintenance screen.
Step 2 On the Maintenance screen, tap Battery Maint, as shown in
Step 3 Tap Start next to Shallow Dis. Test to start a shallow discharge test, as shown in
Figure 5-25 Starting a shallow discharge test
Issue 06 (2020-01-10)
When the battery test is complete, the test data is used as common test data. Record the data obtained
from the latest five tests.
The shallow discharge test automatically stops in any of the following cases:
The battery discharge capacity reaches the specified value (10%–50%, 20% by default).
The discharge voltage reaches the warning threshold (calculated in real time).