UPS5000-E-(25 kVA-125 kVA)
User Manual (25 kVA power modules)
Figure 5-45 Security warning on the LCD
Step 4 Check that the load power is stable (overload due to transient surge may cause the UPS to
transfer to bypass mode), and click Yes.
Step 5 Set the Module cycle hiber. period (d) parameter to an integer ranging from 1 to 100. The
default value is 30.
----End

5.11.2 WebUI

Procedure
Step 1 On the login page, enter a user name and password, and click Login.
Step 2 Choose Monitoring > Param. Settings > Advanced Patameters, as shown in
Figure 5-46 Hibernation parameters on the WebUI
Step 3 On the WebUI, set Paral. sys. hibernate to Enable, and click Submit. A security waning is
displayed, and click OK.
Step 4 Set Module cycle hiber. period (d) to an integer ranging from 1 to 100. The default value is
30.
Issue 06 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
5 Operations