(2) Ethernet setting
Ethernet setting display. (EX600-WEN# only)
•Ethernet setting items.
Description
MAC address
MAC address of the product is displayed.
Select the IP address setting mode. Select the mode suitable for your network environment.
IP address type
IP address
Sets the IP address. (The IP address is valid only when "Manual" mode is selected.)
Select settings for straight cable or crossed cable. Select the settings suitable for your
Auto MDI/MDI-X
environment.
Set Duplex. Select the communication speed suitable for your environment. When the
communication speed is set to automatic mode, it is set automatically regardless of the
Duplex
Duplex setting.
Set the communication speed. Select the communication speed suitable for your environment.
Speed
*1 : Firmware version 1.1.0 or later is required. Refer to 3.2.1. Information tab (page 30) for Firmware version.
*2 : Enable DHCP
: IP address etc. can be obtained from BOOTP/DHCP Server.
If the power is supplied again in this state, information including IP address is obtained
again.
Disable DHCP : IP address etc. cannot be obtained from BOOTP/DHCP Server.
If the power is supplied again with this condition, previous setting can be held.
Manual
: The IP address is set by inputing it directly.
DHCP
: The IP address is set automatically via the DHCP server. Obtained IP
address etc. is lost when the power supply is cut.
*1
Remote Control
: The mode to respond to the commands
provided by Rockwell Automation.
Setting range: Auto/MDIX/MDI
Setting range: Full Duplex/Half Duplex
Setting range: Auto/100 Mbps/10 Mbps