Contents 1. Introduction 1.1. Definition and terminology 2. Preparation before use 2.1. Software Installation 2.2. Before starting the software 2.3. Download the I/O Configurator (NFC version) 2.4. Start the I/O Configurator 3. Window of I/O Configurator (NFC version) 3.1. Basic characteristics 3.1.1.
Page 3
5. Pairing of wireless unit 5.1. Pairing procedure of wireless unit 5.2. Registration of dummy slave 6. Wireless system configuration example 6.1. Flow chart for using the wireless system (Refer to Step 2) 6.2. System Construction Example 6.3. Preparation 6.4. (1) Input and output size of the wireless slave 6.5.
1. Introduction This operation manual describes the installation, construction of screens and operation method of the I/O configurator for NFC. The SMC wireless system I/O Configurator for NFC can be used to check the parameter setting of the wireless unit and the contents and status of the constructed wireless system, using an NFC reader/writer and a PC.
Page 5
: About the communication timing The NFC communication is not accessed all the time. Therefore, it is necessary to update the contents displayed on the screen by clicking the "Refresh button" when reading the parameters. The parameters changed are valid after re-supplying the power supply or by pressing the reset button in the I/O Configurator screen.
1.1. Definition and terminology Term Definition Administrator mode Administrator mode allows the user to configure the wireless units. A broken wire to the input or output equipment has been detected by the diagnostic Broken line detection function. A protocol that automatically allocates information, necessary to be registered to use DHCP the network, such as an IP address, to individual devices connected to the TCP/IP network.
Page 7
Term Definition Occupied points for the module Number of I/O points that can be controlled by a module. input/output Registration of the PID (Product ID) of the wireless slave unit to be connected to the Paring wireless master unit. Registration occurs at the initial setting, then wireless system will activate.
2. Preparation before use 2.1. Software Installation Driver: The following drivers should be installed before using this software. When the SONY Corporation RC-S380/S NFC reader is used (1): Microsoft. Net Framework 4.0 or higher http://www.microsoft.com/en-US/download/details.aspx?id=17718 (2): NFC reader, writer connection driver NFC port software (Ver 5.5.0.6 / Approx.39 MB / Apr.24.2017) https://www.sony.net/Products/felica/business/products/RC-S380.html When the Advanced Card Systems Ltd.
2.2. Before starting the software When the SONY Corporation RC-S380 NFC reader is used, set up the NFC port following the procedure below. When the Advanced Card Systems Ltd. ACR1251U/ACR1252U NFC reader is used, the following setting procedure is not necessary. (1) The NFC setting on the control panel of your PC must be changed as follows.
2.3. Download the I/O Configurator (NFC version) (1) On the SMC website (http://www.smcworld.com), select the Documents/Download and select the Instruction Manuals. (2) Select the Fieldbus System Serial Transmission System. No.EX※※-OMV0017-B...
(3) Select the protocol that the product supports. (Example: EtherNet/IP™ compatible) (4) Scroll down the page of the Fieldbus System Serial Transmission System and select the Configuration File of I/O configurator for NFC. Downloading will begin. 2.4. Start the I/O Configurator (NFC version) Open the downloaded file and double click the IO Configurator.exe to start the I/O configurator for NFC.
3. Window of I/O Configurator (NFC version) In this chapter, the screen display in I/O Configurator (NFC version) in Wireless Master/Slave will be explained. 3.1. Basic characteristics The window below is displayed when the I/O configurator for NFC starts. Place the NFC reader/writer within 1 cm of the centre of the wireless symbol on the wireless unit to display the wireless master/slave information and change the parameter setting.
Page 13
•Basic characteristics Item Explanation When the SONY Corporation RC-S380/S NFC reader is used. NFC setting button When the NFC setting button is clicked, "NFC port/PaSoRi" is displayed on the setting screen. (Refer to 2.2 Before starting the software. (page 8)) The I/O configurator for NFC software version appears by clicking the question mark.
3.1.1. Login to administrator mode Password is necessary to login to the Administrator mode. The Initial password is "admin". In administrator mode It is possible to change the password using "Edit password". For security, change the password for the first time of access. Password check window will open by clicking the Administrator mode.
3.2. Display for wireless master The tabs available on the upper left of the I/O configurator for NFC consists of the Information (page 14), I/O monitor (page 16) and Properties (page 20). 3.2.1. Information tab The Information tab consists of (A) Unit information, (B) System Configuration and (C) Description. (A) Unit information The Unit information area indicates the unit information.
Page 16
(B)System Configuration shows the configuration information of the wireless master/slave module. System configuration Wireless master unit Unit selection Dummy slave (reserved) Error is indicated Wireless slave In System configuration, connected I/O units can be checked by clicking on the displayed wireless unit. (C) Description Description about the unit selected in the System configuration.
3.2.2. Input/Output monitor tab In the I/O monitor tab, the wireless unit I/O map data can be monitored. Diagnosis information or details of input/output can be checked by double clicking each line in the display. Forced output mode (4.3 Forced output (page 58)) can be selected within the Output tab. 3.2.2.1.
Page 18
3.2.2.2. Output tab Output tab shows the output map information of the wireless unit. •Output display Description Content Displayed items Forced output mode can be selected by clicking Enforce ON. Checked : Enforce ON Enforce ON : Refer to 4.3 Forced output (page 58) for the operation. Unchecked : Enforce OFF Address Displays the input map address.
Page 19
3.2.2.3. I/O Detail I/O Detail will open by double clicking the line of the desired address of I/O unit which is connected to the wireless unit. Double-click -18- No.EX※※-OMV0017-B...
Page 20
IO unit information, IO data & diagnostics can all be checked in the IO Detail window. Diagnostic error type is represented by different background colours. The meaning of background colour can be checked by clicking [>>]. •Background colour Background Error Description colour Detection of unconnected load...
3.2.3. Setting tab The configuration of the connected unit can be changed using the setting tab. It consists of setting items (page 21) and the setting display (page 22) (Master setting, Ethernet setting, Slave registration and System setting). Set item Setting display -20- No.EX※※-OMV0017-B...
Page 22
3.2.3.1. Setting items Control panel for setting consists of 4 radio buttons and 3 buttons. •Radio buttons for selecting the required setting window. Description Function Switch to the master unit setting window. Occupied points for the module input/output can Master setting be set.
Page 23
3.2.3.2. Setting display (A) Master unit setting The Master unit setting window. -22- No.EX※※-OMV0017-B...
Page 24
•Master unit setting items Description Explanation Define all settings in the output operation status when the Fieldbus communication is disconnected. CLEAR: Clear the output. Hold/Clear (unit) HOLD: Fix the output at the current value. Software control: Clear, Hold or Set for individual points can be set by software bit. : For details of the Software Control.
Page 25
(B) Ethernet setting Ethernet setting display. •Ethernet setting items. Description Explanation MAC address MAC address of the product is displayed. Select the IP address setting mode. Select the mode suitable for your network environment. IP address setting Manual: The IP address is set by inputing it directly. mode BOOTP/DHCP: The IP address is set automatically via the DHCP server.
Page 26
(C) System setting System setting display. -25- No.EX※※-OMV0017-B...
Page 27
Fixed assignment: Fixed at the number of I/O points set in the System input size and System output size. ※”Auto assignment” is fixed for EX600-WPN※ Set the number of inputs which can be controlled by the entire wireless system. System input size Setting range: 16, 128 to 1280 points (2 to 160 bytes).
Page 28
(D) Slave unit registration Registration for wireless communication between the wireless master unit and the wireless slave unit. For this wireless system, it is necessary to register the PID for each product to establish communication without interference from another network. The window for Slave registration consists of Registered slaves, Save reg.
Page 29
(2) Save registration buttons Buttons used for slave registration. Slave registration buttons are only displayed when wireless units are in pairing mode. •Slave registration buttons Description Content Select the channel used to register the slave to the wireless master. Wireless channel (Only channels available for registration will be displayed) Button to move the wireless slave from Free slaves to Registered slaves.
Page 30
(4) Pairing Details of Pairing. The radio buttons used for pairing are only displayed in Administrator mode. They are grayed out in Monitor mode. They can only be set when power is not supplied. •Details of pairing radio button Description Explanation Button to change to Normal (non-pairing) mode.
3.3. Display for wireless slave The tabs available at the upper left of the I/O configurator for NFC window consists of the Information (page 30), Input/Output monitor (page 32) and setting (page 36). 3.3.1. Information tab The tab for Information consists of (A) Unit information, (B) System configuration and (C) Description. (A) Unit information The unit information area indicates the unit information.
Page 32
(B)System Construction System configuration shows the configuration information of the wireless slave module. Error display: Error is indicated. In System configuration, connected I/O units can be checked by clicking the wireless slave unit. (C) Description Description of the unit selected in the System configuration. The Description is displayed by clicking on the wireless unit or I/O unit in the System configuration.
3.3.2. Input/Output monitor tab In the I/O monitor tab, the wireless unit I/O map data can be monitored. Diagnostic information or details of input/output can be checked by double clicking the line in the display. It is possible to switch between input map and ouput map using the tabs shown.
Page 34
3.3.2.2. Output tab Output tab shows the output map information of the wireless unit. •Output display Description Content Displayed items Address Displays the output map address of the wireless slave. 0 to 15 Wireless CH Wireless unit channel. --, ch001 to 127 Wireless unit PID Individual per unit.
Page 35
3.3.2.3. IO Detail IO Detail will open by double clicking the line of the required address of the IO unit which is connected to the wireless unit. Double-click -34- No.EX※※-OMV0017-B...
Page 36
IO unit information or IO data & diagnostics can be checked in the IO Detail window. The Diagnostic error type is represented by different background colours. The meaning of background colour can be checked by clicking [>>]. •Background colour Background Description Description colour...
3.3.3. Setting tab The configuration of the connected unit can be changed using the setting tab. It consists of setting items (page 37) and setting window (page 38) (Slave setting and Pairing setting). Setting items Setting display -36- No.EX※※-OMV0017-B...
Page 38
3.3.3.1. Setting items Control panel for setting consists of 2 radio buttons and 3 buttons. •Radio buttons for selecting the setting window. Description Function Switch to the slave unit setting display. Occupied points for the module input/output can be Slave unit setting set.
Page 39
3.3.3.2. Setting window (A) Slave unit setting Window for setting slave -38- No.EX※※-OMV0017-B...
Page 40
•Slave setting items Item Explanation Define all settings in the output operation status when the Fieldbus communication is disconnected. CLEAR: Clear the output. Hold/Clear (unit) HOLD: Fix the output at the current value. Software control: Clear, Hold or Set for individual points can be set by software bit. : For details of the Software Control refer to 4.2 Software Control (page 56) for setting in I/O Configurator for NFC) Occupied points for...
(B) Pairing setting Setting for wireless communication between the wireless master unit and wireless slave unit. It is necessary to set the operation mode to Pairing setting when registering the wireless slave to wireless master. Pairing setting display. •Radio button for selecting Pairing mode. Description Explanation Button to change to Normal (non-pairing) mode.
Page 42
(a) Wireless unit Detailed information of the main body and valve can be checked in the wireless unit. a-1). Main body : Refer to 4.1 Edit the tag •Detailed Information (main body) Description Content Part No. Wireless unit product number Wireless unit PID Wireless unit user memo The wireless unit status is displayed in 4 bytes of hexadecimal number.
Page 43
a-2) Valve •Detailed information (valve) Description Content Part No. Wireless master/slave product number Mapped position for the valve. Displays the mapped position of the selected valve. : Refer to the "Unit address order" of (A) Master unit setting (page 22) or (A) Slave unit setting (page 38) Unit No.
Page 44
(b). Digital input unit Digital input unit (product number: EX600-DXD) • Detailed information (digital input unit) Description Content Part No. Displays the product number of the digital input unit which is selected. Displays the mapped position of the selected digital input unit. : Refer to the "Unit address order"...
Page 45
(c). Digital output unit Digital output unit (product number: EX600-DYB) • Detailed information (digital output unit) Description Content Part No. Displays the product number of the selected digital output unit. Displays the mapped position of the selected digital output unit. : Refer to the "Unit address order"...
Page 46
(d). Digital I/O unit Digital output unit (product number: EX600-DMF) • Detailed information (digital input/output unit) Description Content Part No. Displays the product number of the selected digital input/output unit. Displays the mapped position of the selected digital input/output unit. : Refer to the "Unit address order"...
Page 47
(e). Analogue input unit Analogue input (product number: EX600-AXA) Status display: No alarm: (OK) Alarm generated: (Details of error) : Refer to 8.Error Code List on page details of errors. •Detailed information (analogue Input unit) Description Content Part No. Displays the product number of the selected analogue input unit. Displays the mapped position of the selected analogue input unit.
Page 48
(f). Analogue output unit Analogue output (product number: EX600-AYA) Status display: No alarm: (OK) Alarm generated: (Details of error) : Refer to 8. Error Code List on page details of errors. • Detailed information (analogue output unit) Description Content Part No. Displays the product number of the selected analogue output unit Displays the mapped position of the selected analogue output.
Page 49
(g). Analogue I/O unit Analogue input/output unit (product number: EX600-AMB) Status display: No alarm: (OK) Alarm generated: (Details of error) : Refer to 8. Error Code List on page0 details of errors. • Detailed information (analogue I/O unit) Description Content Product No.
3.4.2. Details of I/O monitor tab By clicking the IO Detail tab, the information of the selected unit, diagnostic status, Byte or Bit value , or analogue input/output can be checked. Procedure to display the details of IO unit information I/O monitor tab ...
Page 51
(b). Digital input unit Digital input unit (product number: EX600-DXD) • IO unit information (digital input unit) Description Content Displays the PID of wireless master/slave to which the digital input unit is connected. Displays the tag of wireless master/slave to which the selected digital input unit is connected. Displays the channel name of wireless master/slave to which the selected digital input unit is Wireless channel connected.
Page 52
(c). Digital output unit Digital output unit (product number: EX600-DYB) • IO unit information (digital output unit) Description Content Displays the PID of wireless master/slave to which the selected digital output unit is connected. Displays the tag of wireless master/slave to which the selected digital output unit is connected. Displays the channel name of wireless master/slave to which the selected digital output unit is Wireless channel connected.
Page 53
(d). Digital I/O unit Digital output unit (product number: EX600-DMF) • IO unit information (digital input/output unit) Description Content Displays the PID of wireless master/slave to which the selected digital input/output unit is connected. Displays the tag of wireless master/slave to which the selected digital input/output unit is connected.
Page 54
(e). Analogue input unit Example of analogue input unit (product number: EX600-AXA) IO unit information Status display: No alarm: (OK) Alarm generated: (Details of error) Input/output value of the channel : Refer to 8.Error Code List on page118 for details of errors. •...
Page 55
(f). Analogue output unit Example of analogue output unit (product number: EX600-AYA) IO unit information Status display: No alarm: (OK) Alarm generated: (Details of error) : Refer to 8.Error Code List on Input/output value page118 of the channel for details of errors. •...
Page 56
(g). Analogue I/O unit Example of analogue output unit (product number: EX600-AMB) IO unit information Status display: No alarm: (OK) Alarm generated: (Details of error) : Refer to 8. Error Code List on Input/output value page118 of the channel for details of errors. •...
4. Setting Function There are functions which can be set more easily by using the I/O configurator for NFC for setting. •Edit TAG (page 56) •Software Control(page 56) •Forced output (page 58) •Export of setting (page 63) •Import of setting (page 65) •Reading of the initial value (page 66) •Initialize the product (page 67) 4.1.
Page 58
Hold/Clear setting procedure (1) Details of the output unit information. (Refer to (C) Description (pate 15, 31) to show the detailed information.) Displayed when Software Control is selected. (2) The window for Unit HOLD/CLR/SET setting appears by clicking the Edit button. From the left Bit0,1,2,3,4,5,6,7 -57-...
(3) Upper case letters are used to express the current status of Clear/Hold. The Settable values are C (CLEAR), H (HOLD) or S (SET). Enter 8 characters. When the required values have been entered, click the "Save all" button to store the data. : When CLEAR and HOLD is set for HOLD/CLR/SET, the window below will be displayed.
4.3.2. Forced output procedure This is the forced output procedure using individual bits. Change the tab to I/O monitor to move to forced output mode. Then, click "Enforce ON" on the upper right of the window. Then Click Yes. The window below appears when the mode is changed to forced output mode. Select the output unit to be forced output and double click it.
Page 61
The IO Detail window is displayed. Then, select the Bit (B0 to B7) to be forced output and set to 1. The set value is output by clicking the Enforce button at the bottom of the window. The power supply for output is necessary to activate the output equipment for forced output mode.
Page 62
•Forced output (analogue unit) The window for the forced output for analogue unit is displayed. For forced output for the analogue unit, enter the values according to the analogue range (analogue range can be selected by the I/O configurator for WEB). Enter the values.
4.3.3. Forced output release procedure First, check the box for Enforce ON. Then Click Yes. Click Yes on the following window. Forced output mode is released. Finally. click the Refresh button to update the information in the window. Forced output can also be released by turning off the power supply.
4.4. Export Settings The Export settings tab enables the setting of the unit connected with current NFC reader/writer to be saved to a PC in the format of ".smc". The Import enables the unit setting to be reflected in the other unit. Refer to the table below for settings which can be exported.
Page 65
•Export/import setting Master Slave Item (EX600-WSV#) (EX600-WEN#) (EX600-WPN#) ○ ○ ○ Hold/Clear (unit) ○ ○ ○ Occupied points for the module input ○ ○ ○ Occupied points for the module output Master setting/ Occupied points for the valve manifold ○...
4.5. Import Settings The Import settings tab enables the set file in the format of ".smc" which is save in the PC to be read, and the content of the unit connected with the NFC reader/writer can be changed to the content of the set file. This function is applicable only between the same type of unit (between masters, or between slaves) : Settings to be imported are the same as those to be exported.
4.6. Reading of the initial value Click the "Read factory data" button to initialize or check the parameters in the window currently opened by the setting tab (excluding slave unit registration and pairing setting). In order to reflect the setting, turn off the power and on again or reset when the power is on.
4.7. Initialize Perform Product initialization of the master unit setting or slave unit setting to initialize the product. : After executing the function, this function saves and reflects the setting, and updates the information in the window. The operation is not irreversible.
Page 69
Some values set by the I/O configurator (WEB) are included in the initialized items. Refer to the table below for the set items to be initialized. •Initialized items (I/O Configurator (NFC version)) Master Slave Initialized items (EX600-WSV#) (EX600-WEN#) (EX600-WPN#) ○ ○ ○ Hold/Clear ○ ○ ○...
5. Pairing of wireless unit 5.1. Pairing procedure of wireless unit : Login to the Administrator mode to change to pairing mode. Refer to 3.1.1 Login to administrator mode (page 13). (1) Change the mode of the wireless slave unit to Pairing mode. Change the pairing setting of the wireless slave unit to "Pairing enable"...
Page 71
(2) Change the mode of the wireless master unit to Pairing mode. Change the pairing setting of the slave unit registration of the wireless master unit to "Pairing enable" and reflect the change by clicking Reset module or by re-supplying power. Then, update the contents on the screen by clicking Refresh.
Page 72
(3) Select the wireless channel Register the required wireless channel by registering the slave unit to the wireless master unit. Select the wireless channel and move it from the Free slaves box to Registered slaves box. (Registration is not complete at this point. The status of the wireless slave unit will be shown as "Waiting for registration".) Selected wireless channel is displayed.
Page 73
(4) Determination of the registered information Press Save reg-info to register the wireless slave unit to the wireless master. Then, click Refresh to confirm that the setting has been reflected. (When registration has been completed correctly, the status of the selected wireless slave unit will change from "Waiting for registration"...
Page 74
(5) Change of operation mode of the wireless master unit Change the pairing setting on the slave unit registration screen of the wireless master unit to "Pairing disable" and reflect the change by clicking Reset module or by re-supplying power. Now, the registration procedure for the wireless master unit and the wireless slave unit are complete.
5.2. Registration of dummy slave (1) Change of operation mode of the wireless master unit Change the pairing setting of the slave unit registration of the wireless master unit to "Pairing enable" and reflect the change by clicking Reset module or by re-supplying power. Then, update the contents on the screen by clicking Refresh.
6. Wireless system configuration example The Wireless system configuration method is shown below. Perform the preparation according to section 2. Preparation before use (page 7) before configuring the wireless system. The example below is based on the Step 2 Setting/installation of the wireless unit of 6.1 Flow chart for using the wireless system (page 75) to explaining the Example 1 of 6.2 System Configuration example (page 76).
6.2. System Construction Example An example of the set parameters and memory map of the wire master and slave (2 pcs.) used for wireless system configuration are shown below. Based on the example of Diagnostic allocation of the Operation Manual (page 50). Unit 0 Unit 1 Unit 2...
Page 78
•Memory map Input data Output data Module name Unit name Module name Unit name System diagnosis 1 B (Unit 0) byte0 System diagnosis 2 byte1 EX600-WEN# (Unit 2) Wireless master module Valve output: 16 points System diagnosis 3 byte2 System diagnosis 4 Reserved byte3...
6.3. Preparation STEP 1 Start the I/O Configurator (NFC version) STEP 2 Login to Administrator mode STEP 1 Start the I/O Configurator (NFC version) (1) Start up the I/O Configurator (NFC) and connect the NFC reader/writer to the PC. "R/W detected" will turn on in green when the PC detects the NFC reader/writer.
Page 80
(2) Hold the NFC reader/writer over the wireless slave (1). (3) Click the "Refresh" button to update the information in the Information tab window of the wireless slave (1). Update of the Information tab window -79- No.EX※※-OMV0017-B...
Page 81
STEP 2 Login from the Administrator mode. (1) Click the radio button for Administrator mode. (2) Enter the password in the Password check window. : The default password at the time of shipment from the factory is admin. (3) When the following password input window is displayed, click Confirm. "Password checking passed."...
Page 82
(4) Confirm that the radio button "Administrator mode" is checked during the login state. : The mode is automatically changed to the monitor mode unless a mouse operation is made within 300 seconds in Administrator mode. Window to complete login -81- No.EX※※-OMV0017-B...
6.4. (1) Input and output size of the wireless slave STEP 3 Change of parameter setting (wireless slave (1)) STEP 4 Change to pairing mode (wireless slave (1)) STEP 5 Change of parameter setting (wireless slave (2)) STEP 6 Change to pairing mode (wireless slave (2)) STEP 3 Change of parameter setting (wireless slave (1)) (1) Click the Properties tab to move to the Slave setting window.
Page 84
(3) Change the parameter setting of the wireless slave(1) to the values in the table for parameter setting. (4) Click the "Save all" button to save the set values in the wireless slave (1). Table for the change of parameter setting (wireless slave (1)) Setting items Set value Hold/Clear (unit)
Page 85
(5) The parameter setting of the wireless slave(1) is complete. Slave unit setting window after setting (Wireless slave (1)) -84- No.EX※※-OMV0017-B...
Page 86
STEP 4 Change to pairing mode (wireless slave (1)) (1) Click the radio button for Pairing setting to move to the pairing setting window. From the slave unit setting window to Pairing setting (wireless slave (1)) (2) Click the "Refresh" button to update the information in the Pairing setting window. Pairing setting window (Wireless slave (1)) -85- No.EX※※-OMV0017-B...
Page 87
(3) Click the radio button for Pairing mode. (4) Click Yes to change to the pairing mode. : Slave reset is requested when the mode is changed to pairing mode. The slave cannot be reset when the power supply is not connected.
Page 88
STEP 5 Change of parameter setting (wireless slave (2)) (1) Hold the NFC reader/writer over the wireless slave (2). (2) Click the "Refresh" button to update the window of the wireless slave (2). (3) Click the radio button for Slave setting to move to the Slave unit setting window. From the Pairing setting window to slave unit setting (wireless slave (2)) -87- No.EX※※-OMV0017-B...
Page 89
(4) Click the "Refresh" button to update the information in the Slave setting window for the slave unit. (5) Change the parameter setting of the wireless slave(2) to the values in the table for parameter setting. (6) Click the "Save all" button to save the set values in the wireless slave (2). Table for the change of parameter setting (wireless slave (2)) Setting items Set value...
Page 90
(6) The parameter setting of the wireless slave (2) is complete. Slave unit setting window after setting (Wireless slave (2)) -89- No.EX※※-OMV0017-B...
Page 91
STEP 6 Change to pairing mode (wireless slave (2)) (1) Click the radio button for Pairing setting to move to the pairing setting window. From the slave unit setting window to Pairing setting (wireless slave (2)) -90- No.EX※※-OMV0017-B...
Page 92
(2) Click the radio button for Pairing mode. (3) Click Yes to change to pairing mode. : Slave reset is requested when the mode is changed to pairing mode. The slave cannot be reset when the power supply is not connected.
6.5. Set the number of occupied I/O points for the module and each parameter of the (2) "wireless master" STEP 7 Change of parameter setting STEP7 Change of parameter setting (1) Hold the NFC reader/writer over the wireless master. -92- No.EX※※-OMV0017-B...
Page 94
(2) Click the "Refresh" button to update the window of the wireless master. (3) Click the radio button for the Master setting to move to the master unit setting window. Moves to master unit setting Caution: The Power supply check window appears when power is not supplied to the wireless master. Master unit setting can be changed when power is not supplied.
Page 95
(4) Click the "Refresh" button to update the information in the Master unit setting window. (5) Change the parameter setting of the wireless master to the values in the table for parameter setting. (6) Click the "Save all" button to save the set values in the wireless master. Values for parameter setting Setting items: Set value...
Page 96
(7) The parameter setting of the wireless master is complete. Master unit setting window after setting -95- No.EX※※-OMV0017-B...
6.6. (3) Set the "wireless master" system STEP 8 Change of system setting STEP8 Change of system setting (1) Click the radio button for System setting to move to the system setting window. (2) Click the Refresh button to update the information in the System setting window. Master unit setting window to System setting -96- No.EX※※-OMV0017-B...
Page 98
(3) Change the system settings of the wireless master to the values in the table for system setting. (4) Click the "Save all" button to save the set values in the wireless master. Values for system setting Setting items Set value I/O assignment Automatic assignment System input size...
Page 99
(5) The system setting of the wireless master is complete. System unit setting window after setting -98- No.EX※※-OMV0017-B...
6.7. (7) Ethernet setting for the wireless master Change of Ethernet setting STEP 9 STEP9 Change of Ethernet setting (1) Click the radio button for Ethernet setting to move to the Ethernet setting window. (2) Click the Refresh button to update the information in the Ethernet setting window. System setting window to Ethernet setting -99- No.EX※※-OMV0017-B...
Page 101
(3) Change the Ethernet setting of the wireless master to the Ethernet setting table. : Set the IP address based on the operating network environment. Set the IP address so that the address is not duplicated with other Ehternet equipment. (4) Click the "Save all"...
Page 102
(5) The Ethernet setting of the wireless master is complete. Ethernet setting window after setting -101- No.EX※※-OMV0017-B...
6.8. (4) Registration of wireless slave to the wireless master (pairing) STEP 10 Move the wireless master and slave to Pairing mode STEP 11 Select the wireless slave to be registered STEP 12 The Wireless master gives a command to register the wireless slave STEP 13 Check the wireless connection STEP 10 Move the wireless master and slave to Pairing mode...
Page 104
(4) Click the Refresh button to update the information in the setting tab window. (5) Check that the Power on button in the power supply monitor is green. (6) Click the radio button for Slave registration to move to the Slave unit registration window. From the Ethernet setting window to slave unit registration -103- No.EX※※-OMV0017-B...
Page 105
(7) Click the "Refresh" button to update the information in the Slave registration window. (8) Click the radio button for Pairing mode. (9) Click Yes to change to pairing mode. (10) Click the "Refresh" button to move to Pairing mode. (10) Slave unit registration window (move the wireless master to the Pairing mode) (11) The Pairing status of the wireless master can be checked by the status indication LED: W-NS.
Page 106
(12) Click the Refresh button to update the information in the setting tab window. Click OK in the Pairing mode check window. (12) Update the slave unit registration window (13) Confirm that the wireless slave is displayed in the Free slaves area. (13) Slave unit registration window (check Free slaves) -105-...
Page 107
< Caution > •When the wireless master/slave is moved to pairing mode, the W-SS LED flashes red and green in turn. W-SS indicates the received power level of the connected wireless slave. When the wireless slave and master are connected, the LED turns on and flashes (1Hz/2Hz). Red flashing LED indicates the wireless master is not identified.
Page 108
STEP 11 Select the wireless slave to be registered (1) Select the wireless slave to be registered (1) (PID:07914009) (2) Select the wireless channel (001) of the wireless slave(1) to be registered. (3) Click the "▲". Slave unit registration window (wireless channel: 001 is selected) -107- No.EX※※-OMV0017-B...
Page 109
(4) Select the wireless slave to be registered (2) (PID: 07914002) (5) Select the wireless channel (002) of the wireless slave(2) to be registered. (6) Click the "▲". Slave unit registration window (wireless channel: 002 is selected) (7) Make sure that the registration status is Registered Wait. Slave unit registration window (check the registration status) -108- No.EX※※-OMV0017-B...
Page 110
STEP 12 Wireless master gives a command for registration (1) Click the "Save reg. info". button for the wireless master to send a command for registration. (2) Make sure that the registration status of the wireless slave is Registered. : The pairing mode of the registered wireless slave is automatically released and the wireless slave is reset. Pairing setting becomes unavailable.
Page 111
< How to delete the wireless slave for which registration failed > Perform pairing for the wireless slave which failed registration. In order to register the wireless slave again, it is necessary to delete the wireless slave which failed registration. The procedure to delete is as follows:. (1) Select the wireless slave for which registration failed.
Page 112
STEP 13 Check the wireless connection (1) Click the Normal mode button for Pairing:. (2) Click Yes to change to pairing mode. (3) Click the "Reset" button to release the pairing mode. Slave unit registration window (release the pairing mode of the wireless master) (4) Confirm that wireless communication is established on the status indication LED of the wireless master.
Page 113
(5) Confirm that wireless communication is established on the status indication LED of the wireless slave. •LED: W-NS turns on green when all wireless masters are connected. (6) Click the "Refresh" button to update the information in the Slave registration window. (7) Select the information tab to check that the wireless slaves are connected.
Page 114
(8) Click the Refresh button to update the information tab window. (9) Confirm that the registered wireless slave is displayed in the System configuration. Information tab window (to check the connection of the wireless slave) Configuration of the wireless system is complete. -113- No.EX※※-OMV0017-B...
6.9. Download the configuration file For connecting to the PLC and Ethernet, download the configuration file for the wireless system from the SMC website < Download procedure > On the SMC website (http://www.smcworld.com), select the Documents/Download and select the Instruction Manuals.
Page 116
Select the Fieldbus protocol. (Example: EtherNet/IP™ compatible) Scroll down the page of the Fieldbus System Serial Transmission System and select the Configuration File for SMC Wireless System EtherNet/IP Compatible. Downloading of the configuration file will begin. -115- No.EX※※-OMV0017-B...
7. Wireless system parameter list •Wireless master unit (EX600-WEN#) setting parameters Setting when Classification Parameter name Set value Default Note not energized Setting of output operation status Hold/Clear Clear/Hold/Software control CLEAR Available when the Fieldbus (unit) communication is disconnected. 0 to 128 points (0 to 16 bytes) 128 points/ b) Input size...
Page 118
•Wireless master unit (EX600-WPN#) setting parameters Setting when Classification Parameter name Set value Default Note not energized Setting of output operation status Hold/Clear Clear/Hold/Software control CLEAR Available when the Fieldbus (unit) communication is disconnected. 0 to 128 points (0 to 16 bytes)
Page 119
•Common parameter of wireless master unit and the wireless slave unit Setting when Classification Parameter name Set value Default Note not energized Product No. Letters which can be input are (EX600-WEN#) half-width characters (alphabets, Information Max. 15 letters Available (EX600-WPN#) numbers, symbols) that (EX600-WSV#) correspond to ASCII code. -118- No.EX※※-OMV0017-B...
8. Error Codes Error Message Content Short-circuit detection of load Short circuit of the power supply or load is detected. Detection of unconnected load The valve manifold/output unit load is not connected. Contact operation exceeded the The upper limit of the unit operation cycle has been exceeded. upper limit Exceed the upper limit of the range The upper limit of analogue input range has been exceeded.
9. Troubleshooting Problem Problem Possible causes Investigation and countermeasures 1: Adjust the NFC reader/writer so that it is positioned at the centre of the NFC antenna (circled part). 1. The NFC reader/writer has The wireless master/ 2-1: Remove the NFC reader/writer from the moved away from the slave unit information USB terminal of the PC once and...
Page 122
Problem Problem Possible causes Investigation and countermeasures 1. Connected with a higher Not possible to change to 1. Disconnect the unit from the higher unit. unit. forced output mode. 2. Login from the Administrator mode. 2. Mode is Monitor mode. The wireless slave follows the input/output The wireless slave operates The wireless slave unit...
Notes EX600-WEN※ 2.00 First edition EX600-WSV※ EX600-WPN※ Version for EX600-WPN※ 2.10 EX600-WSV※ EX600-WEN※ Common version for EX600-WEN※ and EX600-WPN※ EX600-WPN※ 2.20 Advanced Card Systems Ltd. reader / writer has been added to verified EX600-WSV※ NFC reader / writer. -122- No.EX※※-OMV0017-B...
Need help?
Do you have a question about the EX600-WPN and is the answer not in the manual?
Questions and answers