ETC Installation Guide
Dual Tech Occupancy Sensor
Settings
The Echo Dual Tech
Ceiling-mount
Occupancy Sensor
participates in an
Echo control system
using the configured
Space and Address,
which are selectable
using the rotary
switches on the sensor electronics located behind the removable cover.
DIP switches and the [MODE] button, also located on the sensor electronics,
set the sensor functionality and the occupancy detection action when set to
Basic configuration mode. See
Note:
DIP switch 2 set to On, all other DIP switch and Mode button settings
are ignored.

Set Space and Address

Two rotary switches on the sensor electronics provide for Space and Address
assignment for the sensor. By default, these switches are set to Space 1,
Address 1. Commands are shared by all devices within a given space.
1. Set the Space rotary switch to the desired number (1 through 16) for
the space you want the sensor to control.
2. Set the Address rotary switch to desired address (1 through 16) for the
sensor identification in the selected space.
Note:
Dual Tech Occupancy Sensor
When the sensor is placed into Custom configuration mode,
Do not duplicate a device Address within the same Space.
Configuration on page 8
Page 6 of 12
DIP switches
Space and Address
switches
.