This procedure is for installing a power-supply module in the PSU1 or PSU2 slot.
Warning
The covers are an integral part of the safety design of the product. Do not operate the unit
without the covers installed. Statement 1077
Warning
This unit might have more than one power supply connection. All connections must be removed
to de-energize the unit. Statement 1028
Equipment installation must comply with local and national electrical codes.
Caution
Equipment That You Need
Note

Grounding the Switch

Follow the grounding procedures at your site and observe these warnings:
78-100604-01
Ratcheting torque flathead screwdriver that exerts up to 15-inch pound (in-lb) of torque
Ring, spade, or flanged spade terminal (terminals should be insulated)
Ring terminal [such as Tyco part number 2-34158-1 for 16–14 AWG (1.31-2.08-mm
2-34852-1 for 12–10 AWG (3.31-5.26-mm
Spade terminal [such as Tyco part number 54367-2 for 16–14 AWG (1.31-2.08 mm
Flanged spade terminal [such as Tyco part number 2-324165-1 for 16–14 AWG
2
(1.31-2.08-mm
) wire or 1-324581-1 for 12–10 AWG (3.31-5.26-mm
For IP-30 compliance:
- Use the 16-14 AWG (1.31-2.08-mm
high-voltage DC power supply
- Use the12-10 AWG (3.31-5.26-mm
power supply
Crimping tool (such as Thomas & Bett part number WT2000, ERG-2001)
6-gauge copper ground wire
2
12-AWG (3.31 mm
) wire (minimum) for the low-voltage power-supply module and 16-AWG
2
(1.31-mm
) (minimum) wire for the high-voltage power-supply module
For power source connections, use wires rated for at least 194°F (90°C).
UL- and CSA-rated style 1007 or 1569 twisted-pair copper wire
Wire-stripping tools for stripping 6-, 10-, 12-, 14-, and 16-gauge wires.
Number-2 Phillips screwdriver
Flat-blade screwdriver
Product Documentation and Compliance for the Cisco IE 5000 Switches—
Documentation produit et conformité pour les commutateurs Cisco IE 5000
2
) wire]
2
) wire and appropriate terminals for the AC or
2
) wire and appropriate terminals for the low-voltage DC
2
) or
2
) wire]
2
) wire]
7

Advertisement

loading