Supported Power Supplies; Installing The Power Converter On A Din Rail, Wall, Or Rack Adapter; Grounding The Switch - Cisco Catalyst IE 3 00 Series Installation Manual

Table of Contents

Advertisement

Supported Power Supplies

Supported Power Supplies
Cisco is constantly updating the IoT Power Supply portfolio. Please refer to the
Switch Data Sheet

Installing the Power Converter on a DIN Rail, Wall, or Rack Adapter

You install the power converter on a DIN rail, wall, or rack as you would a switch module.
Warning
This equipment is supplied as "open type" equipment. It must be mounted within an enclosure that is suitably
designed for those specific environmental conditions that will be present and appropriately designed to prevent
personal injury resulting from accessibility to live parts. The interior of the enclosure must be accessible only
by the use of a tool.
The enclosure must meet IP 54 or NEMA type 4 minimum enclosure rating standards. Statement 1063
Caution
To prevent the switch assemble from overheating, there must be sufficient spacings as explained under
Installation

Grounding the Switch

Make sure to follow any grounding requirements at your site.
Warning
This equipment must be grounded. Never defeat the ground conductor or operate the equipment in the absence
of a suitably installed ground conductor. Contact the appropriate electrical inspection authority or an electrician
if you are uncertain that suitable grounding is available. Statement 1024
Warning
When installing or replacing the unit, the ground connection must always be made first and disconnected last.
Statement 1046
Warning
This equipment is intended to be grounded to comply with emission and immunity requirements. Ensure that
the switch functional ground lug is connected to earth ground during normal use. Statement 1064
Caution
To make sure that the equipment is reliably connected to earth ground, follow the grounding procedure
instructions, and use a UL-listed ring terminal lug suitable for number 10 AWG wire, such as Hollingsworth
part number R3456B or equivalent)
Note
Use at least an 10 AWG (5.26 mm2) conductor to connect to the external grounding screw.
Switch Installation
10
for a comprehensive list of supported power supplies and their capabilities.
Guidelines, between any other switch assembly.