Omron S8FS-C Series Manual page 6

Switch mode power supply
Hide thumbs Also See for S8FS-C Series:
Table of Contents

Advertisement

S8FS-C
Item
Efficiency *
Voltage range *
Frequency *
Current *
Input
Power factor
Leakage current
Inrush current *
(for a cold start at 25°)
Rated Output Current
Voltage adjustment range *
Ripple & Noise
voltage *
Input variation influence *
Load variation influence *
Output
Temperature vari-
ation influence
Startup time *
Hold time *
Overload protection
Overvoltage protection *
Overheat protection
Addi-
Series operation
tional
func-
Parallel operation
tions
Remote sensing
Remote control
Output indicator
Withstand voltage
Insula-
tion
Insulation resistance
Ambient operating temperature
Storage temperature
Envi-
Ambient operating humidity
ronment
Vibration resistance
Shock resistance
MTBF
Reliabil-
ity
Life expectancy *
Dimensions (W×H×D)
Con-
Weight
struc-
Cooling fan
tion
Degree of protection
Harmonic current emissions
EMI
EMS
Stan-
dards
Safety Standards
Marine Standards
SEMI
* Refer to Conditions on page 12.
6
Power rating
Output voltage
5 V
115 VAC input
79% typ.
230 VAC input
80% typ.
Single phase 85 to 264 VAC, 120 to 370 VDC (The L terminal for the DC input is the positive side and safety
standards do not apply.) (Derating is required according to the input voltage. Refer to Derating Curves on page 18.)
50 /60 Hz (47 to 450 Hz)
115 VAC input
0.97 A typ.
230 VAC input
0.59 A typ.
---
115 VAC input
0.25 mA
230 VAC input
0.60 mA
115 VAC input
16 A typ.
230 VAC input
32 A typ.
10 A
−10% to 10% (with V. ADJ)
100 to 240 VAC
80 mVp-p max.
input
0.5% max.
1.0% max.
100 to 240 VAC
0.03%/°C max.
input
115 VAC input
730 ms typ.
230 VAC input
680 ms typ.
115 VAC input
12 ms typ.
230 VAC input
71 ms typ.
Yes, automatic reset
Yes, 115% or higher of rated output voltage, power shut off (shut off the input voltage and turn on the input again)
No
Yes (For up to 2 Power Supplies, external diodes are required.)
No (However, backup operation is possible, external diodes are required.)
No
No
Yes (LED: Green)
3 kVAC for 1 min. (between all input terminals and output terminals) current cutoff 20 mA
2 kVAC for 1 min. (between all input terminals and PE terminals) current cutoff 20 mA
1 kVAC for 1 min. (between all output terminals and PE terminals) current cutoff 20 mA
100 MΩ min. (between all output terminals and all input terminals/PE terminals) at 500 VDC
−20 to 60°C (Derating is required according to the temperature. Refer to Derating Curves on page 17.) (with no
condensation or icing)
−40 to 85°C (with no condensation or icing)
20% to 90% (Storage humidity: 10% to 95%)
10 to 55 Hz, 0.375-mm half amplitude for 2 h each in X, Y, and Z directions
10 to 500 Hz, 0.26-mm half amplitude for 1 h each in X, Y, and Z directions
, 3 times each in ±X, ±Y, ±Z directions
2
150 m/s
135,000 hrs min.
10 years min.
Refer to Dimensions on pages 20 and 24.
300 g max.
No
---
Conforms to EN 61000-3-2, GB17625.1
Conducted
Conforms to EN 61204-3 Class B, EN 55011 Class B, GB9254
Emissions
Radiated
Conforms to EN 61204-3 Class B, EN 55011 Class B, GB9254
Emissions
Conforms to EN 61204-3 high severity levels
Approved Standards
UL : cURus UL 60950-1 (Recognition) OVC II Pol2
CSA: cURus C22.2 No60950-1
CCC: GB4943
Conformed Standards
EN: EN 60950-1 OVC II Pol2
No
No
50 W
12 V
15 V
83% typ.
84% typ.
84% typ.
85% typ.
0.25 mA
0.25 mA
0.55 mA
0.55 mA
4.2 A
3.4 A
110 mVp-p max.
100 mVp-p max.
730 ms typ.
710 ms typ.
670 ms typ.
610 ms typ.
14 ms typ.
14 ms typ.
77 ms typ.
78 ms typ.
24 V
48 V
86% typ.
87% typ.
86% typ.
87% typ.
0.25 mA
0.25 mA
0.55 mA
0.55 mA
2.2 A
1.1 A
100 mVp-p max.
120 mVp-p max.
710 ms typ.
770 ms typ.
640 ms typ.
690 ms typ.
14 ms typ.
14 ms typ.
77 ms typ.
80 ms typ.