Table 3 — 30XA Minimum and Maximum Cooler Flow Rates (cont)
Cooler Leaving Water Temperature*
Cooler Entering Water Temperature†
Nominal Flow Rate
30XA
UNIT SIZE
(gpm)
401
948
450
1019.3
451
1047
476
1104
500
1092.8
501
1184
*For applications requiring cooler leaving water temperature operation at less than 40
F (4.4 C), the units require the use of antifreeze and application may require the brine
option. Contact your local Carrier representative for more information.
†For applications requiring cooler entering water temperature operation at less than 45
F (7.2 C), contact your local Carrier representative for unit selection using the Carrier
electronic catalog.
** For minimum cooler flow rate with brine applications, refer to E-CAT software perfor-
mance.
ITEM
Cooler
(L/s)
Standard, Flooded
59.9
Plus One Pass, Flooded
Minus One Pass, Flooded
Standard, Flooded
64.3
Plus One Pass, Flooded
Minus One Pass, Flooded
Standard, Flooded
66.1
Plus One Pass, Flooded
Minus One Pass, Flooded
Standard, Flooded
69.7
Plus One Pass, Flooded
Minus One Pass, Flooded
Standard, Flooded
68.9
Plus One Pass, Flooded
Minus One Pass, Flooded
Standard, Flooded
74.7
Plus One Pass, Flooded
Minus One Pass, Flooded
MINIMUM
40 F (4.4 C)
45 F (7.2 C)
Minimum Flow Rate**
Number of
Passes
(gpm)
2
474
1
800
1
501
2
523.5
1
800
2
552
1
950
1
501
2
592
1
950
NOTES:
1. The 30XA units will start and pull down with loop temperatures up to 95 F (35 C).
2. Nominal flow rates required at AHRI (Air Conditioning, Heating, and Refrigeration In-
stitute) conditions 44 F (7 C) leaving fluid temperature, 54 F (12 C) entering water
temperature, 95 F (35 C) ambient. Fouling factor 0.00010 ft
K/kW).
3. To obtain proper temperature control, cooler loop fluid volume must be at least 3 gal/
ton (3.23 L/kW) of chiller nominal capacity for air conditioning and at least 6 gal/ton
(6.5 L/kW) for process applications or systems that must operate in low ambient tem-
peratures (below 32 F [0° C]).
118
MAXIMUM
60 F (15 C)
70 F (21.1 C)
Maximum Flow Rate
(L/s)
(gpm)
(L/s)
29.9
1896
119.6
50.5
3792
239.3
31.6
2004
126.4
33.0
2094
132.1
50.5
4000
252.4
34.8
2208
139.3
59.9
4000
252.4
31.6
2004
126.4
37.3
2368
149.4
59.9
4000
252.4
2
-hr-F/Btu (0.000018 m
2
-