Carrier AquaForce 30XA Series Installation Instructions Manual page 114

Air-cooled liquid chillers
Hide thumbs Also See for AquaForce 30XA Series:
Table of Contents

Advertisement

FIELD-SUPPLIED
FUSED DISCONNECT
CONTROL POWER
NOTES:
1. Chiller must be installed level to maintain proper
compressor oil return and hydraulics.
2. Wiring and piping shown are general points-of-
connection guides only and are not intended for a
specific installation. Wiring and piping shown are
for a quick overview of system and are not in
accordance with recognized standards.
3. All wiring must comply with applicable local and
national codes.
4. All piping must follow standard piping techniques.
Refer to Carrier System Design Manual or appro-
priate ASHRAE (American Society of Heating,
Refrigerating, and Air-Conditioning Engineers)
handbook for details.
5. Air separator required as close to chiller as possi-
ble (except primary/secondary systems).
6. 20 mesh strainer required within 10 ft (3 m) of the
cooler in addition to suction strainer for open loop
systems.
Fig. 37B — 30XA Flooded Cooler Typical Piping and Wiring (Units with Hydronic Package)
PRESSURE/
BALANCING VALVE/
TEMPERATURE
SHUTOFF*
TAPS*
VIBRATION
ELIMINATORS*
PUMP
114
AIRFLOW
DRAIN SHUTOFF VALVE
LEGEND
STRAINER*
Airflow Through Condenser
ISOLATION
Power Wiring
VALVE*
Chilled Water Piping
*Field-installed.
FIELD-SUPPLIED
FUSED DISCONNECT
UNIT POWER
A30-4459