Table 5 — 30XA080-500 Electrical Data, Single Point (Standard Condenser Fan Motors) (cont)
UNIT VOLTAGE
NUMBER
UNIT
OF
Supplied
V-Hz
30XA
COND
(3 Ph)
Min Max
FANS
460-60 414
506
22
450
575-60 518
633
22
380-60 342
418
22
460-60 414
506
22
500
575-60 518
633
22
380-60 342
418
22
LEGEND
ICF
— Instantaneous Current Flow
MCA
— Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
WD
— Wye-Delta
XL
— Across-the-Line
NOTES:
1. Units are suitable for use on electrical systems where voltage supplied to the unit terminals
is not below or above the listed minimum and maximum limits. Maximum allowable phase
imbalance is: voltage, 2%; amps 10%.
2. Cooler heater is wired into the control circuit so it is always operable as long as the control
power supply disconnect is on, even if any safety device is open.
3. For MCA that is less than or equal to 380 amps, 3 conductors are required.
For MCA between 381 and 760 amps, 6 conductors are required.
For MCA between 761 and 1140 amps, 9 conductors are required.
For MCA between 1141 and 1520 amps, 12 conductors are required.
Calculation of conductors required is based on 75 C copper wire.
4. Wiring for main field supply must be rated 75 C minimum. Use copper for all units.
a. Incoming wire size range for the terminal block is no. 4 AWG (American Wire Gage) to
500 kcmil.
b. Incoming wire size range of non-fused disconnect with MCA up to 599.9 amps is 3/0 to
500 kcmil.
c. Incoming wire size range of non-fused disconnect with MCA from 600 to 799.9 amps is 1/
0 to 500 kcmil.
d. Incoming wire size range of non-fused disconnect with MCA from 800 to 1199.9 amps is
250 kcmil to 500 kcmil.
5. Data provided circuit 1/circuit 2 where there are two circuits.
6. Standard condenser fan motors are not used with sizes 30XA-401, 451, 476, and 501.
These sizes use high ambient temperature condenser fans.
NO HYDRONIC PACKAGE
ICF
Rec
MCA
MOCP
Fuse
WD
XL
Size
880.0
1000
1080.0 2302.0 1000
674.6
800
847.8 1825.8
800
1022.7
1200
1284.8 2763.8 1200
931.3
1200
1131.3 2353.3 1200
714.1
800
887.3 1865.3
800
1082.4
1200
1344.5 2823.5 1200
5 HP PUMP, 3450 RPM
ICF
Rec
MCA MOCP
Fuse
WD
XL
Size
141
7.5 HP PUMP, 3450 RPM
ICF
Rec
MCA MOCP
Fuse
WD
XL
Size
CONTROL CIRCUIT
Voltage
MCA
1 PH,
and
60 Hz
MOCP
115
60
115
60
115
60
115
60
115
60
115
60