Table 8 — 30XA140-501 Electrical Data, Dual Point (High Ambient Option) (cont)
UNIT VOLTAGE
NUMBER
UNIT
OF
Supplied
V-Hz
30XA
COND
(3 Ph)
Min Max
FANS
230-60 207 253
6/4
200-60 187 220
6/4
140,
460-60 414 506
6/4
142
575-60 518 633
6/4
380-60 342 418
6/4
230-60 207 253
6/4
200-60 187 220
6/4
160,
460-60 414 506
6/4
162
575-60 518 633
6/4
380-60 342 418
6/4
230-60 207 253
6/6
200-60 187 220
6/6
180,
460-60 414 506
6/6
182
575-60 518 633
6/6
380-60 342 418
6/6
230-60 207 253
6/6
200-60 187 220
6/6
200,
460-60 414 506
6/6
202
575-60 518 633
6/6
380-60 342 418
6/6
230-60 207 253
7/6
200-60 187 220
7/6
220,
460-60 414 506
7/6
222
575-60 518 633
7/6
380-60 342 418
7/6
230-60 207 253
7/6
200-60 187 220
7/6
240,
460-60 414 506
7/6
242
575-60 518 633
7/6
380-60 342 418
7/6
460-60 414 506
9/6
260,
575-60 518 633
9/6
262
380-60 342 418
9/6
460-60 414 506
9/7
280,
575-60 518 633
9/7
282
380-60 342 418
9/7
460-60 414 506
10/6
300,
575-60 518 633
10/6
302
380-60 342 418
10/6
460-60 414 506
9/9
325,
575-60 518 633
9/9
327
380-60 342 418
9/9
460-60 414 506
9/9
350,
575-60 518 633
9/9
352
380-60 342 418
9/9
460-60 414 506
8/12
400
575-60 518 633
8/12
380-60 342 418
8/12
460-60 414 506
11/9
401
575-60 518 633
11/9
380-60 342 418
11/9
460-60 414 506
8/14
450
575-60 518 633
8/14
380-60 342 418
8/14
460-60 414 506
13/9
451
575-60 518 633
13/9
380-60 342 418
13/9
460-60 414 506
11/11
476
575-60 518 633
11/11
380-60 342 418
11/11
460-60 414 506
8/14
500
575-60 518 633
8/14
380-60 342 418
8/14
460-60 414 506
14/12
501
575-60 518 633
14/12
380-60 342 418
14/12
LEGEND
ICF
— Instantaneous Current Flow
MCA
— Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
WD
— Wye-Delta
XL
— Across-the-Line
NOTES:
1. Units are suitable for use on electrical systems where voltage supplied to the unit terminals
is not below or above the listed minimum and maximum limits. Maximum allowable phase
imbalance is: voltage, 2%; amps 10%.
2. Cooler heater is wired into the control circuit so it is always operable as long as the control
power supply disconnect is on, even if any safety device is open.
3. For MCA that is less than or equal to 380 amps, 3 conductors are required.
For MCA between 381 and 760 amps, 6 conductors are required.
For MCA between 761 and 1140 amps, 9 conductors are required.
For MCA between 1141 and 1520 amps, 12 conductors are required.
Calculation of conductors required is based on 75 C copper wire.
4. Wiring for main field supply must be rated 75 C minimum. Use copper for all units.
a. Incoming wire size range for the terminal block is no. 4 AWG (American Wire Gage) to
500 kcmil.
b. Incoming wire size range of non-fused disconnect with MCA up to 599.9 amps is 3/0 to
500 kcmil.
c. Incoming wire size range of non-fused disconnect with MCA from 600 to 799.9 amps is 1/
0 to 500 kcmil.
d. Incoming wire size range of non-fused disconnect with MCA from 800 to 1199.9 amps is
250 kcmil to 500 kcmil.
5. Data provided circuit 1/circuit 2 where there are two circuits.
7.5 HP PUMP, 3450 RPM
ICF
MCA
MOCP
WD
383.8/235.1 600/350 660.8/414.4
422.6/259.0 700/400 756.7/473.4
191.9/117.5 300/175 330.4/207.2
962.4/578.2 225/150 191.9/121.1 300/175 330.4/210.8
147.7/ 90.7 225/125 263.9/165.6
769.9 /462.6 175/110 147.7/ 93.5 225/125 263.9/168.4
223.9/138.0 350/200 400.2/251.2
1165.2/700.2 300/175 223.9/142.4 350/200 400.2/255.5
434.8/272.3 700/400 828.8/414.4
478.1/299.6 800/450 950.7/473.4
216.9/135.7 350/200 414.4/207.2
1222.4/578.2 300/175 216.9/139.3 350/200 414.4/210.8
167.0/105.2 250/150 331.9/165.6
977.9/462.6 200/125 167.0/108.1 250/150 331.9/168.4
253.3/159.5 400/250 501.2/251.2
1480.2/700.2 300/200 253.3/163.8 400/250 501.2/255.5
10 HP PUMP, 3450 RPM
Rec
Fuse
MCA
MOCP
XL
Size
450/300 383.8/242.3 600/350 660.8/421.6
500/300 422.6/266.9 700/400 756.7/481.4
600/350 434.8/279.5 700/400 828.8/421.6
600/350 478.1/307.6 800/450 950.7/481.4
153
CONTROL CIRCUIT
ICF
Rec
Voltage
Fuse
1 PH,
WD
XL
Size
60 Hz
450/300
115
500/350
115
962.4/581.8 225/150
115
769.9/465.4 175/110
115
1165.2/704.5 300/175
115
600/350
115
600/400
115
1222.4/581.8 300/175
115
977.9/465.4 200/125
115
1480.2/704.5 300/200
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
MCA
and
MOCP
40
40
40
40
40
40
40
40
40
40
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60