Electrical isolation/isolation of the voltage areas
To provide electrical isolation between the logic level and the I/O area, it is necessary to supply the bus coupler and this safety module from
separate power supply units. Interconnection of the power supply units in the 24 V area is not permitted (see also user manual).
Separate potentials in the system comprising bus coupler/power terminal and safety module
- Test distance
5 V supply incoming remote bus/7.5 V supply (bus logic)
5 V supply outgoing remote bus/7.5 V supply (bus logic)
7.5 V supply (bus logic)/
24 V supply U
, 24 V supply U
M
24 V supply U
, 24 V supply U
M
7.5 V supply (bus logic), relay outputs
COMBICON X3 relay outputs/COMBICON X4 relay outputs, VersaPoint connector relay outputs, 7.5 V supply
(bus logic), 24 V supply U
, 24 V supply U
M
COMBICON X4 relay outputs/COMBICON X3 relay outputs, VersaPoint connector relay outputs, 7.5 V supply
(bus logic), 24 V supply U
, 24 V supply U
M
Approvals
For the latest approvals, please visit http://support.ge-ip.com.
Conformance with EMC Directive 2004/108/EC
Noise immunity test according to DIN EN 61000-6-2
Electrostatic discharge (ESD)
Electromagnetic fields
Fast transients (burst)
Surge voltage
Conducted interference
Noise emission test according to DIN EN 61000-6-4
Noise emission
11-8
, GND, clock outputs, relay outputs, FE
S
, GND, clock outputs/
S
, GND, clock outputs, FE
S
, GND, clock outputs, FE
S
11.3

Conformance with EMC Directive

User manual IC220SDL840 - May 2018
EN 61000-4-2
Criterion B
(IEC 61000-4-2)
6 kV contact discharge, 8 kV air discharge
EN 61000-4-3
Criterion A, field strength 10 V/m
(IEC 61000-4-3)
EN 61000-4-4
Criterion B, test voltage 2 kV
(IEC 61000-4-4)
EN 61000-4-5
Test intensity 2, Criterion B
(IEC 61000-4-5)
DC supply lines:
0.5 kV/0.5 kV (symmetrical/asymmetrical)
Signal lines:
1.0 kV/2.0 kV (symmetrical/asymmetrical)
EN 61000-4-6
Criterion A, test voltage 10 V
(IEC 61000-4-6)
EN 55011
Class A, industrial applications
- Test voltage
500 V AC, 50 Hz, 1 min.
500 V AC, 50 Hz, 1 min.
500 V AC, 50 Hz, 1 min.
500 V AC, 50 Hz, 1 min.
2500 V AC, 50 Hz, 1 min.
2500 V AC, 50 Hz, 1 min.