GE VersaSafe VersaPoint IC220SDL840 User Manual page 47

Module with safe digital relay outputs
Table of Contents

Advertisement

COMBICON connectors
GFK-2734
Insert the assembled connectors in the corresponding module slot (see Section
"Terminal point assignment" on page 3-4).
WARNING: A short circuit between adjacent terminal points can lead to the loss of
the safety function
Ensure that the wires are connected properly. This is essential to prevent the error "short
circuit between adjacent terminal points/cables".
Observe the following points during installation:
Only use cables with a cross section approved for the terminal point (see Section
"General data" on page 11-1).
Observe the current carrying capacity when selecting the cables.
To wire the COMBICON connectors, proceed as follows:
Strip 10 mm off the cable.
For multi-strand cables, fit the stripped cable ends with suitable ferrules and ensure
that they are properly crimped.
Insert the cable in the corresponding terminal point of the connector.
Insert the assembled connectors in the corresponding module slot (see Section
"Terminal point assignment" on page 3-4).
WARNING: A short circuit between adjacent terminal points can lead to the loss of
the safety function
Ensure that the wires are connected properly. This is essential to prevent the error "short
circuit between adjacent terminal points/cables".
Chapter 4 Assembly, removal, and electrical installation
4
4-7