GE VersaSafe VersaPoint IC220SDL840 User Manual page 39

Module with safe digital relay outputs
Table of Contents

Advertisement

Table 3-1
Terminal point assignment for VersaPoint connector X1
Terminal point
1.1
2.1
1.2
OUT0_Ch1_13
2.2
OUT0_Ch2_13
1.3
OUT0_Ch1_14
2.3
OUT0_Ch2_14
1.4
2.4
Table 3-2
Terminal point assignment for VersaPoint connector X2
Terminal point
3.1
4.1
3.2
OUT1_Ch1_13
4.2
OUT1_Ch2_13
3.3
OUT1_Ch1_14
4.3
OUT1_Ch2_14
3.4
4.4
Table 3-3
Terminal point assignment for COMBICON connector X3
Terminal point
5.1
OUT0_Ch1_23
5.2
OUT0_Ch1_24
5.3
OUT0_Ch2_23
5.4
OUT0_Ch2_24
Table 3-4
Terminal point assignment for COMBICON connector X4
Terminal point
6.1
OUT1_Ch1_23
6.2
OUT1_Ch1_24
6.3
OUT1_Ch2_23
6.4
OUT1_Ch2_24
GFK-2734
Chapter 3 VersaPoint potential and data routing, and VersaPoint connectors
Signal
GND
GND
Relay output 0, channel 1, contact 13
Relay output 0, channel 2, contact 13
Relay output 0, channel 1, contact 14
Relay output 0, channel 2, contact 14
UT1
IN1
Signal
U
M
U
S
Relay output 1, channel 1, contact 13
Relay output 1, channel 2, contact 13
Relay output 1, channel 1, contact 14
Relay output 1, channel 2, contact 14
UT2
IN2
Signal
Relay output 0, channel 1, contact 23
Relay output 0, channel 1, contact 24
Relay output 0, channel 2, contact 23
Relay output 0, channel 2, contact 24
Signal
Relay output 1, channel 1, contact 23
Relay output 1, channel 1, contact 24
Relay output 1, channel 2, contact 23
Relay output 1, channel 2, contact 24
"24 V" and "250 V" refer to the relevant voltage ranges (see also Figure 2-3 "Basic
representation of the relay outputs"). For the actual switching voltage ranges, please
refer to the technical data ("Safe digital relay outputs" on page 11-4).
Channel assignment
None
None
Clock output channel 1
Alarm input channel 1
Channel assignment
None
None
Clock output channel 2
Alarm input channel 2
Channel assignment
Channel assignment
Remark
0 V
0 V
24 V
24 V
24 V
24 V
Feedback circuit 1 (external
contact monitoring)
Remark
24 V
24 V
24 V
24 V
Feedback circuit 2 (external
contact monitoring)
Remark
24 V or 250 V
24 V or 250 V
24 V or 250 V
24 V or 250 V
Remark
24 V or 250 V
24 V or 250 V
24 V or 250 V
24 V or 250 V
3
3-5